York PREDATOR MagnaDRY DR090 Technical Manual

York PREDATOR MagnaDRY DR090 Technical Manual

Single package air conditioners and single package gas/electric units
Hide thumbs Also See for PREDATOR MagnaDRY DR090:
Table of Contents

Advertisement

TECHNICAL
GUIDE
MagnaDRY™
SINGLE PACKAGE AIR CONDITIONERS
AND SINGLE PACKAGE GAS/ELECTRIC
UNITS
DR090, 120 and 150
DR090, 120
DR150
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
ASHRAE 90.1 COMPLIANT
®
®
YORK
Predator
MagnaDry™ units are convertible single
packages with a common footprint cabinet and common roof
curb for all 7-1/2 through 12-1/2 ton models. All units have
two compressors with independent refrigeration circuits to
provide 2 stages of cooling. The units were designed for light
commercial applications and can be easily installed on a roof
curb, slab, or frame.
®
All Predator
MagnaDry™ units are self-contained and
assembled on rigid full perimeter base rails allowing for 3-way
forklift access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide a
quick and easy field installation.
All units are convertible between side and down airflow. Inde-
pendent economizer designs are used on side and down dis-
charge applications, as well as all tonnage sizes.
®
Predator
MagnaDry™ units are available in the following
configurations: cooling only, cooling with electric heat, and
cooling with gas heat. Electric heaters are available as fac-
tory-installed options or field-installed accessories.
®
The Predator
MagnaDry™ provides energy-savings, effi-
cient removal of moisture through a balanced coil design.
Because the unit doesn't increase sensible cooling, it allows
temperatures to be maintained within the comfort zone.
Unlike competitive systems, you're not subjected to over
cooling. You save through more efficient matching of dehu-
midification and cooling needs. This makes the MagnaDry™
perfect for applications that need to remove large amounts of
moisture or maintain low humidity levels.
Tested in accordance with:
246721-YTG-C-0606

Advertisement

Table of Contents
loading

Summary of Contents for York PREDATOR MagnaDRY DR090

  • Page 1 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE DESCRIPTION ASHRAE 90.1 COMPLIANT ® ® YORK Predator MagnaDry™ units are convertible single packages with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling.
  • Page 2: Table Of Contents

    DESCRIPTION ........FEATURES ........FACTORY INSTALLED OPTIONS .
  • Page 3 246721-YTG-C-0606 14 ELECTRICAL DATA DR120 WITH PWRD CONVENIENCE OUTLET ......27 15 ELECTRICAL DATA DR150 W/O PWRD CONVENIENCE OUTLET .
  • Page 4: Roof Curbs

    Base rails w/forklift slots (three sides) and lifting holes Roof curbs in eight- and fourteen- inch heights. Roof curbs for transi- tioning from York Sunline™ foot- print to the DH Series footprints Tool-less door latch are also available (field-installed accessory) ®...
  • Page 5: Features

    Base rails w/ forklift slots ( three sides) and lifting holes Roof curbs in eight-and fourteen-inch heights. Roof curbs for transitioning from York Tool-less door Sunline TM footprint to the DM/DH/DJ Series footprint are available (field-installed accessory) ® FIGURE 2 - PREDATOR MagnaDRY™...
  • Page 6: Factory Installed Options

    Compressors and electric heater elements each carry a 5-year warranty. Aluminized steel and stainless steel tubular heat exchangers carry a 10- year warranty. FACTORY INSTALLED OPTIONS ® YORK offers several equipment options factory installed, for ® the Predator line. •...
  • Page 7 246721-YTG-C-0606 • Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The installer needs only to assemble and mount the outdoor air hood (Pro- vided).
  • Page 8: Field Installed Accessories

    • BAS - Building Automation System Controls Simplicity® Intelli-Comfort™ Control - The York Simplicity® Intelli-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field...
  • Page 9: Reheat Mode Sequence Of Operation

    246721-YTG-C-0606 • Power Exhaust - This accessory installs in the unit with a down flow economizer. Power exhaust plugs into the connector in the unit bulkhead. You must purchase 1EH0408 barometric relief when applying to a hori- zontal flow application. •...
  • Page 10 When the room thermostat calls for second stage cooling, the RCB senses a signal through "Y1" & "Y2" and engages circuit #1 and circuit #2 in cooling mode. Indoor blower operation is initiated upon a call for first stage cooling, second stage cooling or dehumidification. Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is a call for dehu- midification at "HUM".
  • Page 11: Reheat Control Board

    246721-YTG-C-0606 eheat Solenoid 3 eheat Terminal Block FIGURE 4 - DR090 & 120 REHEAT CONTROLS Unitary Products Group Unit Control Board eheat Control eheat Board elay eheat Solenoid 1 eheat Solenoid 2 Dehumidistat Terminal...
  • Page 12: Dr150 Reheat Controls

    246721-YTG-C-0606 eheat eheat Pressure Solenoid 1 Switch eheat Solenoid 3 eheat Solenoid 2 eheat elay Unit Control Board eheat Terminal Block eheat Control Board Dehumidistat Terminal FIGURE 5 - DR150 REHEAT CONTROLS Unitary Products Group...
  • Page 13 246721-YTG-C-0606 TABLE 1: ACCESSORIES Part Number 1RC0470 Roof Curb, 8" Height 1RC0471 Roof Curb, 14" Height 1RC0472 Roof Curb, Transition (7.5 T through 12.5 T) 1BD0408 Burglar Bars, Downflow 2TP04520925 Electric Heat 9kW 230V 2TP04521825 Electric Heat 18kW 230V 2TP04522425 Electric Heat 24kW 230V 2TP04523625 Electric Heat 36kW 230V...
  • Page 14: Nomenclature

    NOMENCLATURE 7.5-12.5 Ton York D R 090 N10 A 2 A AA 3 0 1 2 4 A Product Category D = A/C, Single Pkg., R-22 Product Identifier R = REHEAT Nominal Cooling Capacity 090 = 7.5 Ton 120 = 10.0 Ton 150 = 12.5 Ton...
  • Page 15: Physical Data

    246721-YTG-C-0606 TABLE 2: PHYSICAL DATA Component Blower, Centrifugal (Dia. X Wd. In.) Evaporator Motor, Standard (HP) Blower Motor, Optional (HP) Evaporator Coil Reheat Coil Propeller Dia. (in., each) Condenser Fan CFM, Nominal (each) Condenser Coil Face Area (ft.2 each) Refrigerant Charge Compressors Size (Wd.
  • Page 16: Dr Capacity Ratings

    TABLE 3: DR CAPACITY RATINGS Cooling Capacity ARI Ratings Size Model IPLV Cooling Only Electric 11.2 11.65 Heat Gas Heat Gas Heat Cooling Only Electric 11.2 11.40 Heat Gas Heat Gas Heat Cooling Only Electric 11.1 11.7 Heat Gas Heat Gas Heat Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
  • Page 17: Cooling Capacity Dr090 Unit

    246721-YTG-C-0606 TABLE 5: COOLING CAPACITY DR090 UNIT Air On Temperature of Air on Condenser Coil 85°F Evap. Coil Total Tot. † WB (°F) Cap. Input (MBH) (kW) 2250 2625 3000 3375 3750 Temperature of Air on Condenser Coil 105°F 2250 2625 3000 3375...
  • Page 18: Cooling Capacity Dr090 Unit (Alternate Reheat Mode)

    TABLE 6: COOLING CAPACITY DR090 UNIT (ALTERNATE REHEAT MODE) Air On Evap. Coil Temperature of Air on Condenser Coil 85°F Tot. Total † WB (°F) Cap.* Input (MBH) (kW) 2250 2625 3000 3375 3750 Temperature of Air on Condenser Coil 105°F 2250 2625 3000...
  • Page 19: Cooling Capacity Dr120 Unit

    246721-YTG-C-0606 TABLE 7: COOLING CAPACITY DR120 UNIT Air On Evap. Coil Temperature of Air on Condenser Coil 85°F Total Tot. WB (°F) Cap. Input (MBH) (kW) 3000 3500 4000 4500 5000 Temperature of Air on Condenser Coil 105°F 10.0 3000 10.1 3500 10.1...
  • Page 20: Cooling Capacity Dr120 Unit (Alternate Reheat Mode)

    TABLE 8: COOLING CAPACITY DR120 UNIT (ALTERNATE REHEAT MODE) Air On Evap. Temperature of Air on Condenser Coil 85°F Coil Total Tot. Cap. Input (°F) (MBH) (kW) 3000 3500 4000 4500 5000 Temperature of Air on Condenser Coil 105°F 3000 3500 4000 4500...
  • Page 21: Cooling Capacity Dr150 Unit

    246721-YTG-C-0606 TABLE 9: COOLING CAPACITY DR150 UNIT Air On Evap. Coil Temperature of Air on Condenser Coil 85°F Total Tot. WB (°F) Cap. Input (MBH) (kW) 10.9 10.7 3750 10.5 10.7 10.9 10.7 4375 10.6 10.7 11.0 10.7 5000 10.6 10.7 11.0 10.8...
  • Page 22: Cooling Capacity Dr150 Unit (Alternate Reheat Mode)

    TABLE 10: COOLING CAPACITY DR150 UNIT (ALTERNATE REHEAT MODE) Air On Evap. Coil Temperature of Air on Condenser Coil 85°F Total Tot. WB (°F) Cap. Input (MBH) (kW) 10.7 10.2 3750 10.5 10.0 4375 10.3 5000 10.4 5625 10.6 10.1 6250 Temperature of Air on Condenser Coil 105°F 11.8...
  • Page 23: Dr090 Moisture Removal - Alternate Mode

    246721-YTG-C-0606 FIGURE 6 - DR090 MOISTURE REMOVAL - ALTERNATE MODE FIGURE 7 - DR090 MOISTURE REMOVAL - NORMAL MODE Unitary Products Group DR090 Moisture Removal @ 3000 cfm Alternate Mode @ various indoor (dry bulb / wet bulb) conditions Outdoor Temperature (°F) 75db/71wb 80db/71wb 85db/71wb...
  • Page 24: Dr120 Moisture Removal - Alternate Mode

    FIGURE 8 - DR120 MOISTURE REMOVAL - ALTERNATE MODE FIGURE 9 - DR120 MOISTURE REMOVAL - NORMAL MODE DR120 Moisture Removal @ 4000 cfm Alternate Mode @ various indoor (dry bulb / wet bulb) conditions Outdoor Temperature (°F) 75db/71wb 80db/71wb 85db/71wb 80db/67wb DR120 Moisture Removal @ 4000 cfm...
  • Page 25: Dr150 Moisture Removal - Alternate Mode

    246721-YTG-C-0606 FIGURE 10 - DR150 MOISTURE REMOVAL - ALTERNATE MODE FIGURE 11 - DR150 MOISTURE REMOVAL - NORMAL MODE Unitary Products Group DR150 Moisture Removal @ 5000cfm Alternate Mode @ various indoor (dry bulb / wet bulb) conditions Outdoor Temperature 75db/71wb 80db/71wb 75db/67wb...
  • Page 26: W/Power Exhaust

    TABLE 11: ELECTRICAL DATA DR090 W/O PWRD CONVENIENCE OUTLET OD Fan Supply Blower Compressors Motors Motor FLA Voltage 13.1 110.0 13.1 110.0 54.0 44.0 Maximum HACR breaker of the same AMP size is applicable. TABLE 12: ELECTRICAL DATA DR090 WITH PWRD CONVENIENCE OUTLET OD Fan Supply Blower Compressors...
  • Page 27: Electrical Data Dr120 W/O Pwrd Convenience Outlet

    246721-YTG-C-0606 TABLE 13: ELECTRICAL DATA DR120 W/O PWRD CONVENIENCE OUTLET OD Fan Supply Blower Compressors Motors Motor FLA Voltage 16.0 137.0 16.0 137.0 69.0 58.0 Maximum HACR breaker of the same AMP size is applicable. TABLE 14: ELECTRICAL DATA DR120 WITH PWRD CONVENIENCE OUTLET OD Fan Supply Blower Compressors...
  • Page 28: Exhaust

    TABLE 15: ELECTRICAL DATA DR150 W/O PWRD CONVENIENCE OUTLET OD Fan Supply Blower Compressors Motors Motor FLA Voltage 20.0 146.0 10.9 16.1 20.0 146.0 10.9 16.1 73.0 60.0 Maximum HACR breaker of the same AMP size is applicable. TABLE 16: ELECTRICAL DATA DR150 W/PWRD CONVENIENCE OUTLET OD Fan Supply Blower Compressors...
  • Page 29: Blower Performance Dr090 Sideflow

    246721-YTG-C-0606 TABLE 18: BLOWER PERFORMANCE DR090 SIDEFLOW ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----...
  • Page 30: Blower Performance Dr090 Sideflow Economizer

    TABLE 19: BLOWER PERFORMANCE DR090 SIDEFLOW ECONOMIZER DR090 Standard Drive Assembly (Side Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 3886 846 1588 1.70 3655 807 0.4 3709 847...
  • Page 31: Blower Performance Dr090 Downflow

    246721-YTG-C-0606 TABLE 20: BLOWER PERFORMANCE DR090 DOWNFLOW ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP ---- ---- ---- ---- ---- ---- 0.3 3619 853 1468 1.57 3328 814 0.4 3385 854 1402 1.50 3094 815...
  • Page 32: Blower Performance Dr090 Downflow Economizer

    TABLE 21: BLOWER PERFORMANCE DR090 DOWNFLOW ECONOMIZER DR090 Optional Drive Assembly (Down Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP ---- ---- ----...
  • Page 33: Blower Performance Dr120 Sideflow

    246721-YTG-C-0606 TABLE 22: BLOWER PERFORMANCE DR120 SIDEFLOW ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 ---- ---- ---- ---- ---- ---- 0.4 ---- ---- ---- ---- 4507 896 2044 2.19 4167 857 1768 1.90 3864 818 1531 1.64 3599 780 1332 1.43 3372 741 1171 1.26 0.5 ---- ----...
  • Page 34: Blower Performance Dr120 Sideflow Economizer

    TABLE 23: BLOWER PERFORMANCE DR120 SIDEFLOW ECONOMIZER DR120 Standard Drive Assembly (Side Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 ---- ---- ---- ---- ---- ----...
  • Page 35: Blower Performance Dr120 Downflow

    246721-YTG-C-0606 TABLE 24: BLOWER PERFORMANCE DR120 DOWNFLOW ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.2 4755 914 2162 2.32 4436 875 0.3 4455 915 2034 2.18 4136 877 0.4 4213 917 1935 2.08 3894 879...
  • Page 36: Blower Performance Dr120 Downflow Economizer

    TABLE 25: BLOWER PERFORMANCE DR120 DOWNFLOW ECONOMIZER DR120 Standard Drive Assembly (Down Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.2 4461 915 2037 2.19 4050 878 0.3 4216 917...
  • Page 37: Blower Performance Dr150 Sideflow

    246721-YTG-C-0606 TABLE 26: BLOWER PERFORMANCE DR150 SIDEFLOW ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.5 ---- ---- ---- ---- ---- ---- 0.6 ---- ---- ---- ----...
  • Page 38: Blower Performance Dr150 Sideflow Economizer

    TABLE 27: BLOWER PERFORMANCE DR150 SIDEFLOW ECONOMIZER DR150 Standard Drive Assembly (Side Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.4 ---- ---- ---- ---- ---- ----...
  • Page 39: Blower Performance Dr150 Downflow

    246721-YTG-C-0606 TABLE 28: BLOWER PERFORMANCE DR150 DOWNFLOW ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----...
  • Page 40: Blower Performance Dr150 Downflow Economizer

    TABLE 29: BLOWER PERFORMANCE DR150 DOWNFLOW ECONOMIZER DR150 Standard Drive Assembly (Down Flow) (100% Return Economizer) ESP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP CFM RPM WATT BHP 0.3 ---- ---- ---- ---- ---- ----...
  • Page 41: Additional Static Resistance

    246721-YTG-C-0606 TABLE 30: ADDITIONAL STATIC RESISTANCE Gas Heat 2300 0.08 2500 0.09 2700 0.11 2900 0.12 3100 0.14 3300 0.16 3500 0.18 3700 0.20 3900 0.23 4100 0.25 4300 0.28 4500 0.30 4700 0.33 4900 0.36 5100 0.39 5300 0.42 5500 0.45 5700...
  • Page 42: Unit Center Of Gravity Dr090, 120

    LEFT FIGURE 12 - DR090, 120 UNITS 4 POINT LOAD LEFT FIGURE 13 - DR090, 120 UNITS 6 POINT LOAD TABLE 34: 4 POINT LOAD WEIGHT Location (lbs.) Model DR090 DR120 DR150 (090) 23" (090) 38" 25-1/2" 47-1/2" LEFT FIGURE 14 - UNIT CENTER OF GRAVITY DR090, 120 FRONT LEFT FIGURE 15 - DR150 UNIT 4 POINT LOAD...
  • Page 43: Dr090/120 Unit Dimensions

    246721-YTG-C-0606 TABLE 36: UNIT WEIGHT Shipping Model Weight (lbs.) DR090 1163 DR120 1277 DR150 1560 W/ECON. W/PE W/ELECT. HEAT W/GAS HEAT 54 KW Heater 8 Tube Heat Exchanger 30-11/32 50-3/4 4-1/4 30-3/16 24-3/16 LEFT FIGURE 18 - DR090/120 UNIT DIMENSIONS Unitary Products Group Operating Weight (lbs.)
  • Page 44: Dr150 Unit Dimensions

    30-11/32 4-1/4 50-3/4 30-3/16 LEFT FIGURE 19 - DR150 UNIT DIMENSIONS DETAIL A TABLE 37: UNIT CLEARANCES 72” Right Front Left 36” 36” Rear Bottom Units must be installed outdoors. Overhanging structure or shrubs should not obstruct condenser air discharge outlet. To remove the slide-out drain pan, a rear clearance of 60”...
  • Page 45: Predator ® Roof Curb Dimensions

    246721-YTG-C-0606 ® FIGURE 20 - PREDATOR ROOF CURB DIMENSIONS ® FIGURE 21 - SUNLINE™ TO PREDATOR TRANSITION ROOF CURBS Unitary Products Group...
  • Page 46: Bottom Duct Openings (From Above)

    6-13/16 LEFT 21-3/16 19-3/16 17-3/16 7-1/8 14-23/32 16-3/8 18-1/16 FIGURE 22 - BOTTOM DUCT OPENINGS (FROM ABOVE) 18-1/4 5-5/32 FIGURE 23 - DR090, 120 REAR DUCT DIMENSIONS 32-11/16 6-13/16 Supply Return 27-1/2 FRONT Bottom Bottom Condensate Power, Control and Drain Convenience Outlet 19-5/8 Wiring Entries...
  • Page 47: Dr150 Rear Duct Dimensions

    246721-YTG-C-0606 18-1/4 5-5/32 FIGURE 24 - DR150 REAR DUCT DIMENSIONS 58 1/4 39 1/2 47 1/2 Outside Air Intake Hood 35 3/4 FIGURE 25 - DOWNFLOW ECONOMIZER HOOD DETAIL Unitary Products Group Supply 28-1/4 88 1/4 25 3/4 18-1/4 Plugs Return 28-1/4 18-1/16...
  • Page 48: Downflow Economizer Hood Detail

    58-¼" 47-½" OUTSIDE AIR INTAKE HOOD FIGURE 26 - DOWNFLOW ECONOMIZER HOOD DETAIL TABLE 38: ECONOMIZER USAGE Application Cabinet Height Bottom Return Side Return 42" ERV or End Return 50" Barometric relief must be ordered seperately and installed in duct work. Barometric relief or fresh air hood not included.
  • Page 49: Factory Installed Downflow Economizer

    246721-YTG-C-0606 2EE04705424 2EE04705424 2EE04705424 2EE04705424 2EE04705424 Fresh Air Hood Fresh Air Damper Return Air Damper Barometric Relief Damper Barometric Relief Hood FIGURE 27 - FACTORY INSTALLED DOWNFLOW ECONOMIZER 2EE04705424 2EE04705424 2EE04705424 2PE047032XX Fresh Air Hood Fresh Air Damper Return Air Damper Power Exhaust 2EE04705424 2EE04705424...
  • Page 50: Field Installed Horizontal Economizer W/Power Exhaust

    Field Installed Duct Work 2PE047032XX Power Exhaust 1EH0408 Barometric Relief Damper FIGURE 29 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST 2EE04705X24 Slab Economizer FIGURE 30 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST 2EE04705524 Return Air Damper 1EH0408 Barometric Relief Hood 2PE047032XX Power Exhaust 1EH0409 Barometric Relief Damper...
  • Page 51: Slab Economizer End Return W/Power Exhaust

    246721-YTG-C-0606 1EH0409 Fresh Air Hood Field Installed Duct Work 2EE04705X24 Slab Economizer 1EH0409 Barometric Relief Hood 2PE047032XX 1EH0409 Power Exhaust Barometric Relief Damper FIGURE 31 - SLAB ECONOMIZER END RETURN W/POWER EXHAUST Unitary Products Group...
  • Page 52: Typical Low Voltage Field Wiring

    THERMOSTAT TERMINALS TO REMOTE SENSOR 2ET04701324 IF USED Electronic programmable Thermostat 2ET0770010024 ( includes subbase). Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set-back position. Dehumidistat closes on rise in humidity. FIGURE 32 - TYPICAL LOW VOLTAGE FIELD WIRING ( RCB ) REHEAT...
  • Page 53: Field Wiring Disconnect-Cooling Unit With

    246721-YTG-C-0606 GROUND FIGURE 33 - FIELD WIRING DISCONNECT-COOLING UNIT WITH/WITHOUT ELECTRIC HEAT GROUND FIGURE 34 - FIELD WIRING DISCONNECT-COOLING UNIT WITH GAS HEAT Unitary Products Group TERMINAL BLOCK TB1 FACTORY OR FIELD SUPPLIED DISCONNECT CONTACTOR 1M FACTORY OR FIELD SUPPLIED DISCONNECT THREE PHASE POWER...
  • Page 54: Dr090, 120 Cooling Unit With Gas Heat

    246721-YTG-C-0606 FIGURE 35 - DR090, 120 COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM Unitary Products Group...
  • Page 55: Dr150 Cooling Unit With Gas Heat Wiring 230 Volt Diagram

    246721-YTG-C-0606 FIGURE 36 - DR150 COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM Unitary Products Group...
  • Page 56: Dr090, 120 Cooling Unit With/Without Electric Heat Wiring Diagram

    246721-YTG-C-0606 FIGURE 37 - DR090, 120 COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM Unitary Products Group...
  • Page 57: Dr150 Cooling Unit With/Without Electric Heat Wiring Diagram

    246721-YTG-C-0606 FIGURE 38 - DR150 COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM Unitary Products Group...
  • Page 58: Dr090, 120 Cooling Unit With Gas Heat Wiring 460, 575 Volt 50 Hz Diagram

    246721-YTG-C-0606 FIGURE 39 - DR090, 120 COOLING UNIT WITH GAS HEAT WIRING 460, 575 VOLT 50 HZ DIAGRAM Unitary Products Group...
  • Page 59: Dr150 Cooling Unit With Gas Heat Wiring 460, 575 & 50 Hz Diagram

    246721-YTG-C-0606 FIGURE 40 - DR150 COOLING UNIT WITH GAS HEAT WIRING 460, 575 & 50 HZ DIAGRAM Unitary Products Group...
  • Page 60 246721-YTG-C-0606 FIGURE 41 - DR090 AND 120 REHEAT WIRING DIAGRAM Unitary Products Group...
  • Page 61 246721-YTG-C-0606 FIGURE 42 - DR150 REHEAT WIRING DIAGRAM Unitary Products Group...
  • Page 62: Guide Specifications

    GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK® ® Predator MagnaDRY™ units are convertible single pack- ages with a common footprint cabinet and common roof curb for all 7-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to pro- vide 2 stages of cooling.
  • Page 63 246721-YTG-C-0606 Refrigerant Circuit and Refrigerant Safety Components shall include: Independent fixed-orifice or thermally operated expan- sion devices. Solid core filter drier/strainer to eliminate any moisture or foreign matter. C. Accessible service gage connections on both suction and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
  • Page 64 ECONOMIZER (Downflow and Horizontal flow) • POWER EXHAUST – (Unit mount – Downflow, Duct mount – Horizontal flow) • DUAL ENTHALPY KIT - Provides a second input to economizer to monitor return air. Supersedes: 246721-YTG-B-0305/036-21551-001-B-0305 5005 York Drive 246721-YTG-C-0606 Norman 73069...