Electric Heating Function Of Chassis; Electric Heating Function Of Compressor - Daikin FTKS18SL216 Service Manual

Split r410a series
Table of Contents

Advertisement

Service Manual

6. Electric Heating Function of Chassis

(1) When Toutdoor amb.≤32ºF , the electric heating of chassis will operate;
(2) When Toutdoor amb.>35.6ºF , the electric heating of chassis will stop operation;
(3)When 32ºF <Toutdoor amb.≤35.6ºF, the electric heating of chassis will keep original status.

7. Electric Heating Function of Compressor

(1) When Toutdoor amb.≤≤23ºF , compressor stops operation, while the electric heating of compressor starts operation;
(2) When Toutdoor amb.>28.4ºF , the electric heating of compressor stops operation;
(3) When 23ºF <Toutdoor amb.≤28.4ºF , the electric heating of compressor will keep original status.
Technical Information
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents