Energy Pack
The CPE302 preserves user memory using an Energy Pack without the need
to periodically replace batteries. The IC695ACC400 Energy Pack powers the
CPU long enough for the CPU to write its user memory contents to the
CPU's non-volatile storage during a system power loss. Installation of the
Energy Pack is found below.
Light-Emitting Diode Indicators (LEDs)
OK — indicates module readiness to perform normal operations.
Green, ON
steady
OFF
Green, blinking
RN — indicates the run state of the CPU.
7
PACSystems™ RX3i Central Processing Unit IC695CPE302
CPU passed power-up diagnostics, functioning
properly
Power is not applied, or CPU has a problem,
which may be indicated by RN and EN blink
pattern
CPU in Stop-Halt state; possible watchdog
timer fault. Refer to the fault tables. If the
programmer cannot connect, cycle power
with a charged Energy Pack attached and refer
to fault tables
Green, ON
CPU is in Run mode.
steady
OFF
CPU is in Stop mode.
GFK-3038B