Flame Signal Measurement; Final Checks (With The Burner Working) - Riello RS 190/E Installation, Use And Maintenance Instructions

Table of Contents

Advertisement

5.6

Flame signal measurement

Check the flame signal through the parameter 954, as indicated in
Fig. 37. The displayed value is expressed in percentage.
The value during the operation must be higher than 24%. If at the
burner start-up the value is higher or equal of 18%, the burner locks
out due to the extraneous light.
For further and specific information, please refer to the specific
instruction manual. The display (Fig. 37) shows parameter 954:
flashing on the left.
5.7

Final checks (with the burner working)

➤ Open the control limit operation
➤ Open the high limit operation
➤ Rotate the maximum gas pressure switch knob to the mini-
mum end-of-scale position
➤ Rotate the air pressure switch knob to the maximum end of
scale position
➤ Switch off the burner and disconnect the voltage
➤ Disconnect the minimum gas pressure switch
➤ Cover the UV flame sensor
Make sure that the mechanical locking systems on
the different adjustment devices are fully tightened.
WARNING
20052068
Start-up, calibration and operation of the burner
30
On the right, the flame's intensity is displayed as a percentage.
Example: 954: 0.0
S8171
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to firing failure
GB
P
V
h min s
%
Fig. 37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

C9327400C932741020094407

Table of Contents