For the complete relay technical data, see www.dold.com.
Pt100 relays
■
GM International D1073S
Ordering information
Model
Programming tool (not included in the ABB delivery)
Power supply (terminals 3-4)
Rated voltage
Voltage range
Maximum power consumption
Measuring circuit (terminals 13-16)
Sensor type
Integration time
Resolution
Visualization
Input range
Measuring RTD current
RTD line resistance compensation
RTD line resistance error compensation
Current output (terminals 1-2)
Signal range (span)
Resolution
Transfer characteristic
Response time
Output ripple
Output contacts (terminals 5-8)
Number of contacts
Hysteresis
ON-OFF delay time
Contact rating
Performance
Ref. Conditions 24 V supply, 250 ohm load, 23 ±1 °C surrounding air temperature
D1073S
GM Pocket Portable Configurator PPC1090, or RS-232
serial line with PPC1092 Adapter and SWC1090
Configurator software (recommended).
24 V DC reverse polarity protected
20 ... 30 V DC
2.1 W at 30 V supply voltage, overload condition, relays
energized and PPC1090 connected
3-4 wire RTD Pt100 (for other alternatives, see the relay
data sheet)
500 ms
5 μV on mV, 20 mohm on RTD, 0.05% on transmitting
potentiometer
0.1 °C on temperature, 10 μV on mV, 0.1% on
potentiometer
within rated limits of sensor (-10 mV ... +80 mV).
≤ 0.5 mA
≤ 10 ohm
-5 ohm ... +20 ohm, programmable
0/4 ... 20 mA, on max. 600 ohm load source mode,
current limited at 22 mA
2 μA current output or 1 mV voltage output
linear or reverse
≤ 50 ms (10...90% step change)
≤ 20 mVrms on 250 ohm load
Two SPST relay contacts
0 ... 5 °C for temperature sensor input, 0 ... 50 mV for
mV input, 0 ... 50% for potentiometer input (see input
for step resolution).
0 ... 1000 s, 100 ms step, separate setting
2 A / 250 V AC / 500 VA
2 A / 250 V DC / 80 W (resistive load)
Technical data 59