H I - S E I Sm I C Instantan Eous Un I T; H Ig H Drop Out; Hi- Seismic Target And Seal -In Unit - GE IFC66A Instructions Manual

Time overcurrent relays
Table of Contents

Advertisement

Mech anic al Adju stme nt
The disk does not have to be in the exact center of either air gap for the relay to perform correc tly .
Should the disk not clear all gaps , the following adjustment can be made.
l .
Determine which way the disk must be aligned to clear all gap surfac es by 0 . 0 10 inch .
Remove the drag magnet assembly by loosening the two screws securing it to the support structure .
2 .
need
The screws
Loosen the upper pivot bearing set screw (l/ 16 inch hex wrench) slightly, s o the upper pivot can
3 .
move freely .
4 .
Loosen the jewel bearing set screw as in 3 above.
Apply a slight downward finger pressure on the upper pivot and turn the jewel bearing screw, from
5 .
the underside of the support structure, to position the disk as determined in 1 above.
6 .
Turn the jewel bearing screw 1/8 turn clockwise and tighten the upper pivot set screw to 2 . 5 - 3.5
inch pounds of torque.
7.
Turn the jewel bearing screw 1/8 turn counterclockwise .
assembly approximately 0 . 005 inch and permit proper end -play.
of end -play .
8 .
Tighten the jewel
9.
Rotate the disk through the electromagnet gap.
inch and be within 0 . 005 inch flatness .
should be replaced.
Reinstall the drag magnet assembly and check that the disk has at least 0 . 0 10 inch clearance from
10 .
the drag magnet assembly surfaces .
1 1.
Tighten the drag magnet assembly mounting screws with 7 - 10 inch pounds of torque, after securely
seating thL: assembly and positioning it according to the TIME T E ST above.
HI- SEISMIC INSTANTANEOUS U NIT AND HIGH
1 .
Both contacts should close at the same time .
2.
The backing strip should be so formed that the forked and (front) bears against the molded strip
under the armature .
3 .
With the armature against the pole piece, the eros::. member of the "T" spring should be in a­
horizontal plane and there should be at least 1/6 4" inch wipe on the contacts .
inserting a 0 . 0 10 inch feeler gage between front half of the shaded pole with the armature held
closed. Contacts should close with feeler gage in place .
4.
Since mechanical adjustments may affect the Seismic Fragility Le vel, it is advised that no
m�chanical adjustments be made if seismic capability is of concern .

HI- SEISMIC TARGET AND SEAL -IN UNIT

Check l and 2 as described under INSTANTANEOUS UNIT .
To check the wipe of the seal-in unit, insert a 0.0 10 inch feeler gage between the plastic residual of
armature and the pole piece with the armature held closed .
Since mechanical adjustments may affect the Seismic Fragility Level, it is advised that no mechanical
adjustments be made if seismic capability is of concern.
not be removed .
Do not remove the set screw from the support structure.
bearing set screw to 2 . 5 - 3.5 inch pounds of torque.
DROP OUT INSTANTANEOUS U N I T
GEK-45376
This will lower the disk and shaft
The shaft must have 0 . 005 -0.0 10 inch
The disk should clear the gap surfaces by 0 . 010
If the disk is not within 0.005 inch flatness the disk
Contacts should close with feeler gage in place .
15
Check this by

Advertisement