  • Page 1 VIPA Networking Solutions PBR | 920-1CA50 | Manual HB153 | PBR | 920-1CA50 | en | 19-09 PROFIBUS MultiRepeater A5 www.vipa.com/en/service-support/manuals...
  • Page 2 VIPA GmbH Ohmstr. 4 91074 Herzogenaurach Telephone: +49 9132 744-0 Fax: +49 9132 744-1864 Email: info@vipa.com Internet: www.vipa.com 920-1CA50_000_PBMR-A5,4,GB - © 2019...
  • Page 3: Table Of Contents

    VIPA Networking Solutions Table of contents Table of contents General........................4 1.1 Copyright © VIPA GmbH ................. 4 1.2 About this manual..................... 5 1.3 Safety information..................... 5 Product Description....................7 2.1 General......................7 2.2 Product features....................8 2.3 Application areas....................9 2.4 Additional Benefits....................
  • Page 4: General

    VIPA Networking Solutions General Copyright © VIPA GmbH General 1.1 Copyright © VIPA GmbH All Rights Reserved This document contains proprietary information of VIPA and is not to be disclosed or used except in accordance with applicable agreements. This material is protected by the copyright laws. It may not be reproduced, distributed, or altered in any fashion by any entity (either internal or external to VIPA), except in accord- ance with applicable agreements, contracts or licensing, without the express written con- sent of VIPA and the business management owner of the material.
  • Page 5: About This Manual

    VIPA Networking Solutions General Safety information Information product sup- Contact your local VIPA Customer Service Organization representative if you wish to port report errors or questions regarding the contents of this document. If you are unable to locate a customer service centre, contact VIPA as follows: VIPA GmbH, Ohmstraße 4, 91074 Herzogenaurach, Germany Telefax: +49 9132 744-1204 EMail: documentation@vipa.de...
  • Page 6 VIPA Networking Solutions General Safety information CAUTION! The following conditions must be met before using or commis- sioning the components described in this manual: – Hardware modifications to the process control system should only be carried out when the system has been disconnected from power! –...
  • Page 7: Product Description

    VIPA Networking Solutions Product Description General Product Description 2.1 General The PROFIBUS MultiRepeater A5 is advanced, flexible and robust network components for PROFIBUS DP installations, to implement long multi-device spur lines and backbone structures with star/tree segments. PROFIBUS DP is a high speed communication bus that has to comply with strict rules concerning spur lines, because of possible reflections that could lead to communica- tion disturbances.
  • Page 8: Product Features

    VIPA Networking Solutions Product Description Product features 2.2 Product features 5 Galvanic isolated channels (repeater segments) Transparent for all PROFIBUS DP protocols DP-RS485 specifications for each channel Cable redundancy for channel 1+2 9.6 Kbps to 12 Mbps 31 devices per channel 1200 m spur line length (depends on transmission speed) No limit in serial placement or cascading of MultiRepeaters No address required...
  • Page 9: Application Areas

    VIPA Networking Solutions Product Description Channel Structure 2.3 Application areas Dynamic spur lines to actuators, flow meters and pH analyzers Removable drives and motors Pull/Plug motor control centres (drawers) Roof mounted devices in tank farms Dirty and humid environments Barrier for non-galvanic isolated equipment Large star/tree structured networks Outdoor applications with device and cable stress 2.4 Additional Benefits...
  • Page 10: Grounding System

    VIPA Networking Solutions Product Description Cable lengths for PROFIBUS DP 2.6 Grounding System The PROFIBUS MultiRepeater can be grounded by 3 methods: Direct grounding on the Ground Rail Indirect grounding (through a capacitor) Combination of direct and indirect The power supply must be grounded directly on the Ground Rail. The shielding of the PROFIBUS cables can be directly or indirectly grounded.
  • Page 11: Cable Types For Profibus Dp

    VIPA Networking Solutions Product Description Cable types for PROFIBUS DP 2.8 Cable types for PROFIBUS DP The cable type must comply with the PROFIBUS DP cable specifications for RS485. Parameter Value Wires 2 (twisted) Impedance 135 ... 165 Ohm (3 to 20 MHz) Capacity <...
  • Page 12: Status Display

    VIPA Networking Solutions Product Description Status display 2.9 Status display The Status LEDs on the PROFIBUS MultiRepeater 920-1CA50 are very useful for diag- nostics. Blinking POWER Power is not switched on or Power supply not stable or Power supply OK an internal failure an internal failure Main READY...
  • Page 13: Installation Instructions

    VIPA Networking Solutions Installation Instructions Mounting Installation Instructions 3.1 Location The PROFIBUS MultiRepeater A5 can be installed everywhere in a non-hazardous area that complies with IP 65 (DIN 40 050) and the specified temperature range of -40 ... +75° Celsius. 3.2 Position Der PROFIBUS MultiRepeater A5 can be installed in every position, but it is recom- mended to install it with the cable glands pointing down to create a more reliable protec-...
  • Page 14: Power Supply

    VIPA Networking Solutions Installation Instructions Backbone 3.4 Power Supply The 4-pin screw type power connector is located on the bottom left of the PCB: Power LEDs Power connector The power supply must comply with the following specifications: Voltage: 10 - 32V DC Current: min.
  • Page 15 VIPA Networking Solutions Installation Instructions Backbone Bus-In Connector Communication status LED Bus-Out Connector Pin layout of the screw Wiring terminals Green wire Red wire Cable shielding Shield Cable shielding Connecting the indirect cable shielding is not required when the ground clips are used.
  • Page 16: Spur Segments

    VIPA Networking Solutions Installation Instructions Termination 3.6 Spur Segments Connect the spur segments to the connectors of Channel 1 to 5. Communications status LEDs Channel connector Pin layout of the screw Wiring terminals Green wire Red wire Cable shielding Shield Cable shielding Testing If a Channel recognizes valid PROFIBUS messages from one or more connected...
  • Page 17: Baudrate Switch

    VIPA Networking Solutions Installation Instructions Baudrate switch Don’t forget to switch the termination ON at the other end of the segment and make sure it is powered continuously. 3.8 Baudrate switch The PROFIBUS MultiRepeater A5 recognizes the transmission speed by default. If it is required that the MultiRepeater is locked to a certain transmission speed, the baudrate switch should be set to the required value.
  • Page 18: Technical Data

    VIPA Networking Solutions Technical data Technical data Order no. 920-1CA50 Dimensions and weight Dimensions L x H x D (mm) with screws 213 x 210 x 95 mm Weight Weight Approx. 800 g Mounting screws 4 to 5 mm Ambient conditions Operating temperature -40 ...
  • Page 19 VIPA Networking Solutions Technical data Order no. 920-1CA50 400 m at 500 kbps 200 m at 1.5 Mbps 100 m at 3 Mbps to 12 Mbps Cable thickness 6 to 12 mm Wire diameter < 2.5 mm Wire type Stranded or Solid core Number of devices Maximum 31 per Channel (including MultiRepeaters, OLMs, Laptops/ PCs, etc)
  • Page 20: Glossary

    VIPA Networking Solutions Glossary Glossary Address Unique number of a device connected to the network. With PROFIBUS this can be 0 to 126. 127 is a broadcast address. Analyzer Software tool to observe the protocol traffic. Combi-Analyzers can also inspect the signal quality.
  • Page 21 VIPA Networking Solutions Glossary Multiple Protocol Interface. Protocol defined by Siemens which uses the layer 1 and 2 of PROFIBUS (FDL). Printed Circuit Board PROFIBUS DP Acronym for "PROFIBUS for Decentralized Peripherals". Specification of an open fieldbus system with the following characteristics: Polling master-slave-system (cyclic communications, MS0) Flying masters with robin round token passing coordination (MM) Connection based (MS1) and connectionless (MS2, MS3) acyclic communication between...