ERROR
DESCRIPTION
DD
Heating / Cooling Mode Conflict
Communication Error Between
E1
Indoor & Outdoor Unit
E2, E4,
Check Temperature Sensor
E5
E6
DC Fan Motor
E7
EEPROM Error (Data Storage)
Communication Error Between
E9
Indoor Unit and Controller
EB
EEV Error
ED
Outdoor Unit Error
EE
Condensate Error
No Address When Power ON for first
FE
time
UU
MDC Auto System-Check Mode
LEGEND
EEV
— Electronic Expansion Valve
EEPROM — Electronically Erasable Programmable Read-only Memory
— Multiport Distribution Controller
MDC
PC
— Process Controller

Replacement Parts

Quote the unit model number and unit serial number when
ordering replacement parts or contacting the factory about the
unit. This information can be found on the serial plate attached
to the unit. See Fig. 41.
Table 6 — Troubleshooting
POSSIBLE CAUSES
System is in cooling or fan only mode and
heating signal is received from a unit on the
system.
System is in heating mode and cooling
signal is received from a unit in the system.
Signal wires are short-circuited or
disconnected.
Signal wire close to electromagnetic
source.
PC board fault.
Loose connection at port on PC board.
Sensor is short-circuited.
PC board fault.
Operating beyond limits.
DC motor fault.
PC board fault.
Chip or PC board fault.
Signal wires are short-circuited or
disconnected.
Signal wires close to electromagnetic
source.
PC board fault.
EEV wires are short-circuited or
disconnected.
EEV stop.
PC board fault.
Outdoor unit fault.
Loose connection or disconnected.
Water level float is stuck.
Trap slope is too steep.
Drain pipe is too long.
Drain pump faulty.
Indoor unit without address.
MDC fault
25
POSSIBLE SOLUTIONS
All units should be in cooling mode for system to
stay in cooling mode.
All units should be in heating mode.
Check or reconnect signal wire.
Distance signal wires from electromagnetic
source.
Replace PC board.
Tighten the connection at port on PC board.
Using multi-meter, measure resistance of the
sensor. If the resistance is £ 100 ohms, change
the sensor.
Replace PC board.
Check and correct external static pressure on the
unit.
Replace DC motor.
Replace PC board.
Replace PC board.
Check or reconnect signal wires.
Distance signal wires from electromagnetic
source.
Replace PC board.
Replace EEV wires.
Replace EEV.
Replace PC board.
Refer to outdoor unit troubleshooting guide.
Tighten the connection or reconnect at port on
PC board.
Inspect the slope.
Adjust the trap slope.
Adjust the length of drain pipe.
Replace the drain pump.
Run automatic addressing option at the outdoor
unit.
Use remote wireless or wired controller to
readdress indoor unit.
Refer to MDC troubleshooting guide.
CONFORMS TO UL STD 1995
CERTIFIED TO CSA STD.
C22. 2 No. 236
ELECTRIC CHARACTERISTICS ARE
ONLY FOR INDOOR UNIT.
MEDIUM STATIC DUCT UNIT
MODEL
POWER SUPPLY
MINIMUM CIRCUIT AMPACITY
MAX FUSE OR HACR BREAKER
FLA
FAN MOTOR
OUTPUT
REFRIGERANT
HIGH
DESIGN
PRESSURE
LOW
SERIAL NO.
1716V00001
Carrier Corporation
Fig. 41 — Unit Serial Plate (Example)
3124627
40VMM007A--3
208/230V-1Ph-60Hz
1.25 A
15 A
1 A
100W (1/6HP)
R410A
580 PSIG
320 PSIG