e) While the indoor unit thermostats are displayed, press the SET (SW007) key. The display changes to indoor
unit forced thermostat OFF setting. Select the indoor units that are to be forced OFF. (* Set this setting from
the smallest address unit of the corresponding refrigerant system.)
* A light turns on to indicate that the thermostat of the corresponding indoor unit is ON, blinks at 1-second
intervals to indicate the thermostat of the corresponding indoor unit is OFF, blinks at 0.5-second intervals to
indicate the forced thermostat OFF setting is set for the corresponding indoor unit, and blinks at high speed
to indicate the number of the indoor unit being set.
* Use the UP (SW005) or DOWN (SW006) key to select the number of the indoor unit to be forced to stop. The
screen automatically switches to display units 33–64 for numbers exceeding 32.
f) After selecting the number of the indoor unit to be forced to stop, press the SET (SW007) key for longer than 1
second. The forced thermostat OFF setting is set for the selected indoor unit. TEST/WARNING indicator (red
LED (LED052)) lights up.
In order to cancel the forced stop, after selecting the number of the indoor unit, press the SET (SW007) key
for longer than 1 second. The forced thermostat OFF setting is canceled for the selected indoor unit. TEST/
WARNING indicator (red LED (LED052)) goes off.
g) After completing the tests, remove the setting.
● Check that there is no error metallic noise from the compressor.
● Check that there is no error metallic noise or tappet noises from the engine.
 Check that there is no error vibration in each part of the units.
● Check that there is no error vibration in the refrigerant tubing or capillary tubes. (particularly during low rota-
tional speeds)
● Check that there are no error vibrations due to contact between tubing, fittings, panels, etc.
a) For safety, when the outdoor units are stopped, set the total stop setting (Set SW001 (STOP-SW) to "STOP")
on all outdoor main boards of the corresponding refrigerant system.
(3) Checking the indoor units and remote controller
● Stop the outdoor unit test run and remove the forced thermostat OFF setting on the indoor units. (turn the Stop
switch (STOP SW) to "NORM")
● With each remote controller individually, check that the combination of indoor unit and remote controller unit num-
ber display label agree.
Unit 25
Unit 26
Unit 1
Unit2 Unit 3
Unit 4 Unit 5
Unit 13
Unit14 Unit 15
Unit 16 Unit 17
Unit 31
Unit 32
Unit 57
Unit 58
Unit 33
Unit 34 Unit 35
Unit 36 Unit 37
Unit 45
Unit 46 Unit 47
Unit 48 Unit 49
Unit 63
Unit 64
Unit 27
Unit 28
Unit 29
Unit 6 Unit 7
Unit 8 Unit 9
Unit 18 Unit 19
Unit 20 Unit 21
Unit 59
Unit 60
Unit 61
Unit 38 Unit 39
Unit 40 Unit 41
Unit 50 Unit 51
Unit 52 Unit 53
Figure 7
Ⅲ-4
Unit 30
Unit10 Unit 11
Unit 12
Unit22 Unit 23
Unit 24
Unit 62
Unit42 Unit 43
Unit 44
Unit 54 Unit 55
Unit 56