PER Series 3 Electric-Hydronic Boilers Installation Instructions
Ratings
DOE
Boiler
DOE heating
Boiler input
model
capacity
number
BTU/Hr
PER-15
51,000
PER-20
68,000
PER-25
85,000
Notes:
1. Provide manual shutoff valves in the system piping at the supply outlet and the return inlet so the boiler can be drained without draining the entire
system.
2. For other than the standard voltages shown, consult Weil-McLain Application Engineering Department.
3. Copper wire (AWG-MCM). Consult national or local electrical code manuals for runs in excess of 50 feet. Do no use aluminum wire.
4. All ratings are based on 240-volt power input. See Figure 1 for percent of boiler capacity when the input voltage is below 240 volts. Gross output
ratings. Piping loss not confined to the heated area should be added to the building loss to determine total heating equipment.
Figure 1
Boiler capacities at various voltages
100%
90%
80%
70%
60%
200
210
Input Voltage
39601
Part number 550-141-396/0801
Required wire sizes and weights
Number of
Element size
elements
KW
KW
15
3
5
20
4
5
25
5
5
220
230
240
Total
Volts phase
Wire size
amperes
wire
90˚C field
wiring
(Note 2)
(Note 3)
65
240/1/3
86
240/1/3
107
240/1/3
Boiler
Approximate
water
shipping wt.
content
Gallons
lbs.
4
5.2
215
3
5.2
215
1
5.2
215
13