Connect Device To The Supply Voltage - Siemens SIPART DR22 Assembly And Installation Information

Hide thumbs Also See for SIPART DR22:
Table of Contents

Advertisement

Available languages

Available languages

7.4

Connect Device to the Supply Voltage

D 6DR2210-5
6DR2410-5
L
N
PE
115 or 230 V AC
Figure 8 Wiring of the auxiliary power supply 230 V/115 V
D 6DR2210-4
6DR2410-4
per device T3,15A
24 V UC
Figure 9 Wiring of the auxiliary power supply 24 V
WARNING
!
To guarantee high electromagnetic compatibility (EMC), the ground
conductor screw (grounding screw 8, Figure 2) must be connected
to the ground of the equipment (cupboard, grounding rails).
This connection must also be low-ohm for high frequencies (Cu
band or HF litz wire, at least 2.5 mm
SIPART DR22/DR24
C79000-M7474-C38-01
(A C230 V/115 V )
Power supply connector
per device T1A
Other users on the
same
circuit; increase
fuse power slightly
(UC 24 V)
Other users on the
same
circuit; increase
fuse power slightly
Assembly and Installation Information
IEC 320 IV
DIN 49457A
230
L
N
PE
6DR2210-5
6DR2410-5
Alternativ
Double-pole special plug;
any polarity
~
6DR2210-4
6DR2410-4
2
).
115
+
~
+
U
=
+
+
U
REF
=
24 V
5 V
REF
24 V
5 V
23

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Sipart dr246dr2210-46dr2210-56dr2410-46dr2410-5