Siemens SED2 VFD NEMA Operating Instructions Manual page 44

Bypass
Hide thumbs Also See for SED2 VFD NEMA:
Table of Contents

Advertisement

SED2 VFD NEMA Type 3R/3RHE Bypass Operating Instructions
Parameter
Description
P0700(0)**
Selection of Command Source
(Start Command)
Selects the command source as
follows:
0 = Factory default setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link (AOP)
5 = USS on COM link
6 = CB (Communications board
or module) on COM link (P1/N2)
NOTE:
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 to 2
resets all digital inputs to default settings.
P0700[1]**
Selection of Command Source
(Start Command)
Selects the command source as
follows:
0 = Factory default setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link (AOP)
5 = USS on COM link
6 = CB (Communications board
or module) on COM link (P1/N2)
NOTE:
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 to 2
resets all digital inputs to default settings.
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.
36
Action
1.
Press
to advance to
parameter P0700.
2.
Press
to access the
parameter indexes.
3.
Press
to advance to index
[0], IN000, AUTO.
4.
Press
to confirm index
selection.
5.
Press
to advance to 2.
6.
Press
to confirm and save
the setting.
1.
Press
to advance to index
[1], IN001, HAND.
2.
Press
to confirm index
selection.
3.
Press
to advance to 1.
4.
Press
to confirm and save
the setting.
5.
Press
again to return to the
parameter selection level.
Setting/Default
Setting = 2
Default = 2
Setting = 1
Default = 1
Siemens Building Technologies, Inc.