Navien NFC-175 Installation & Operation Manual page 79

Nfc condensing combi-boilers
Hide thumbs Also See for NFC-175:
Table of Contents

Advertisement

9.6.3 Direct Vent Application – Horizontal
Installation
In cases where a 12" horizontal clearance is not possible, provide a
vertical clearance of at least 36" with the exhaust above the intake
but do not exceed 20' .
i n .
m ) m
0 0 m
1 2 " ( 3
Exhaust Gas
Intake Air
Exhaust
Maximum
length 20'
(6 m)
Minimum
length 36"
Intake
(91 cm)
The illustration is intended for reference purposes
Note
only.
Direct the exhaust away from any building
openings.
During cold weather situations, the temperature of
the exhaust will be much warmer than the ambient
air. Therefore, you will see water vapor being
produced at the termination.
Installing a Common Vent System
79