Installation Guidelines

WARNING
High pressure! Injury to skin and eyes, possible! Be careful when opening connections on a pressurized item.
Compressor Handling
Delivery
Please check whether the delivery is correct and complete. Any deficiency should be reported immediately in writing.
Suction and discharge shut-off valves
Oil charge, oil sight glass
Mounting kit
CoreSense™ Diagnostics module
Holding charge up to 2.5 bar(g) (dry air)
Transport and Storage
WARNING
Risk of collapse! Personal injuries! Move compressors only with appropriate mechanical or handling equipment according to
weight. Keep in the upright position. Stack and transit as shown below. Keep the packaging dry at all times.
Compressors are delivered on pallets. Cooling fans are delivered in separate cartons. Accessories may be mounted or delivered loose.
Solenoid valves are never mounted.
Positioning and Securing
IMPORTANT
Handling damage! Compressor malfunction! Only use the lifting eyes whenever the compressor requires positioning. Using
discharge or suction connections for lifting may cause damage or leaks.
If possible, the compressor should be kept vertical during handling. For safety reasons, two lifting eyes should be fitted before moving a
compressor (½" - 13 UNC). Otherwise refer to drawings on Figure 5 to see how to apply other lifting methods.
4M*
max. 220 kg
In order to avoid refrigerant leaks or other damage the compressors should not be lifted by the service valves or other accessories.
12
STOCK
TRANSIT
3
2
Figure 4
6M*
max. 260 kg
Figure 5