Electrical Data - Friedrich VRP Series Installation & Operation Manual

Variable refrigerant packaged heat pump
Hide thumbs Also See for VRP Series:
Table of Contents

Advertisement

Electrical Data

VRP Model
Voltage
230
208
230
VRP12K
208
230
208
VRP12R
265
230
208
230
208
230
VRP24K
208
230
208
230
208
VRP24R
265
MCA = Minimum Circuit Ampacity
MOP / MOCP - Maximum Overcurrent Protection / Breaker Size
Minimum Circuit Amps (MCA) and MOCP values in the above table are calculated in accordance with The NEC.Article 440
Electrical Requirements
Use ONLY wire size recommended for
Wire Size
single outlet branch circuit.
Fuse/Circuit
Use ONLY type and size fuse or HACR cir-
Breaker
cuit breaker indicated on unit's rating guide.
Proper over current protection to the units is
the responsibility of the owner.
Grounding
Unit MUST be grounded from branch circuit
to unit, or through separate ground wire
provided on permanently connected units.
Ensure that branch circuit or general pur-
pose outlet is grounded.
Wire Sizing
Use recommended wire size given in tables
and install a single branch circuit. All wiring
must comply with local and national codes.
NOTE: Use copper conductors only.
NOTE: All field wiring must comply with NEC and local codes. It is the installer's responsibility to ensure that the electrical codes are
met.
Electric
Electric
Heater
Heating
ID Blower
Watts
Btu
Amps
2500
8530
0.34
2030
6980
0.38
3400
11601
0.34
2780
9480
0.38
5000
17060
0.34
4100
13980
0.38
2500
8530
3400
11601
5000
17060
2500
8530
0.77
2030
6980
0.85
3400
11600
0.77
2780
9480
0.85
5000
17050
0.77
4100
13980
0.85
7500
25590
0.77
6130
20900
0.85
10000
34120
0.77
8180
27890
0.85
2500
8530
3400
11601
5000
17060
7500
25590
10000
34120
Total
Electric
OD Blower
Heating
Amps
Amps
0.42
11.2
0.42
10.2
0.42
15.1
0.42
13.8
0.42
22
0.42
20.1
0.2
0.40
9.8
0.2
0.40
13.2
0.2
0.40
19.3
0.60
11.6
0.60
10.7
0.60
15.6
0.60
14.3
0.60
22.6
0.60
20.6
0.60
33.4
0.60
30.4
0.60
44.3
0.60
40.2
0.7
0.60
10.8
0.7
0.60
14.2
0.7
0.60
20.3
0.7
0.60
29.7
0.7
0.60
39.1
Electrical Rating Table
NOTE: Use copper conductors ONLY. Wire sizes are per NEC.
Recommended Branch Circuit Sizes*
Nameplate Maximum Circuit Breaker Size
15A
20A
30A
AWG - American Wire Gauge
* Single circuit from main box.
** Based on 100' or less of copper, single insulated conductor at 60˚ C
MCA
MOP / MOCP
14.0
15
18.9
20
27.5
30
12.3
15
16.5
20
24.1
25
14.5
15
19.5
20
28.3
30
41.8
45
55.4
60
13.5
15
17.8
20
25.4
25
37.1
40
48.9
60
AWG Wiring Size**
14
12
10
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrp12kVrp12rVrp24kVrp24r