Default I/O Connections - ABB ACS355 Quick Installation Manual

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Installing the control cables

Default I/O connections

1...10 kohm
max. 500 ohm
1)
AI1 is used as a speed reference if vector mode is
selected.
2)
See parameter group 12 CONSTANT SPEEDS:
DI3 DI4
Operation (parameter)
0
0
Set speed through AI1
1
0
Speed 1 (1202)
0
1
Speed 2 (1203)
1
1
Speed 3 (1204)
3)
0 = ramp times according to parameters 2202 and
2203.
1 = ramp times according to parameters 2205 and
2206.
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency reference: 0...10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Not in use by default. 0...10 V
6
GND
Analog input circuit common
7
AO
Output frequency value: 0...20 mA
8
GND
Analog output circuit common
4)
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
Forward (0) / Reverse (1)
14 DI3
Constant speed selection
15 DI4
Constant speed selection
16 DI5
Acceleration and deceleration selection
X1B
17 ROCOM
18 RONC
19 RONO
20 DOSRC
21 DOOUT
22 DOGND
X1C:STO
1
OUT1
STO (Safe torque off) connection
2
OUT2
3
IN1
4
IN2
Quick installation guide – ACS355 5
Relay output 1
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
4)
360 degree grounding under a clamp.
Tightening torque = 0.4 N·m / 3.5 lbf·in.