Install the FIPS Opacity Shield in a Two-Post Rack

Step 7
Use the captive screws on the front of the mounting brackets to fully secure the chassis to the rack.
What to do next
• See
• Install the cables according to your default software configuration as described in the
Install the FIPS Opacity Shield in a Two-Post Rack
Caution
This procedure should be performed only by the Crypto Officer (CO).
Note
Because the FIPS opacity shield covers the serial number on the chassis, the CO should copy the serial number
and store it in a secure place. The serial number is needed when you call Cisco TAC.
Before you begin
You need the following to install the FIPS opacity shield:
• #1 Phillips head screwdriver
• The following items from the FIPS kit:
Step 1
Copy the serial number and store in a secure place. To find the serial number, see
Cisco Firepower 2100 Series Hardware Installation Guide
56
Ground the Chassis, on page 62
for your version.
• One FIPS opacity shield
• Four 8-32 x .375-in. countersink screws used to attach the FIPS opacity shield to the cable
management brackets
• Seven Tamper Evidence Labels (TEL)
Note
The TELs are made of a special thin gauge vinyl with self-adhesive backing.
Once the CO attaches them on the chassis, any attempt to open the chassis damages
the TELs or the chassis cover. Because the TELs have nonrepeated serial numbers,
the CO can inspect them for damage and compare them against the applied serial
numbers to verify whether the chassis has been tampered with. TELs with curled
corners, rips, and slices indicate tampering. The word "FIPS" or "OPEN" may
appear if the label has been peeled back.
for the procedure to ground the Firepower 2100.