GE Mark VIeS System Manual page 334

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

117, 126
Description JPDF-[ ] fuse FU1S or FU2S (J1S connector) is blown or SW1S switched OFF
Possible Cause
The SW1R is turned off and FuseDiag is enabled.
The FU1S or FU2S fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
118, 127
Description JPDF-[ ] fuse FU1T or FU2T (J1T connector) is blown or SW1T switched OFF
Possible Cause
The SW1R is turned off and FuseDiag is enabled.
The FU1T or FU2T fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
334
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents