Download Print this page

T&S EC-TMV Installation Instructions

Thermostatic mixing valve

Advertisement

Quick Links

EC-TMV & 5EF-TMV
Thermostatic Mixing Valve
Installation Instructions
Models EC-TMV and 5EF-TMV are a direct replacement Thermostatic
Mixing Valve (TMV) for the Mechanical Mixing Valve used on ChekPoint
(EC) and Equip (5EF) Electronic Faucets. These TMV's are tested
and certifi ed to ASSE 1070. These TMV's will control and limit the
temperature of tempered water to the faucet. They are equipped
with an adjustable and lockable means to limit the maximum outlet
temperature with the intention of reducing the risk of scalding.
NOTE: This device is pre-set for approximately 100˚F (38˚C). This device must be adjusted, verifi ed and locked
to a specifi c maximum temperature at the time of installation.
TOOLS NEEDED
Adjustable wrench
#2 Phillips Screwdriver
Thermometer
INSTALLATION
1. Turn off Hot and Cold water supply to the faucet.
2. Disconnect the Hot and Cold fl ex supply hoses at the mechanical mixing valve.
3. Loosen and unscrew the swivel nut connecting the Mechanical Mixing Valve to the fi tting on the Control Module.
Remove the Mechanical Mixing Valve.
4. Install the outlet side of the TMV (MIX) into the swivel nut connection on the Control Module and tighten.
5. Connect and tighten the Hot and Cold fl ex supply hoses to the corresponding Hot (H) and Cold (C) inlets of the TMV.
6. Turn on Hot and Cold water supply and check for leaks.
ADJUSTMENT
1. Activate the faucet several times until the outlet water temperature stabilizes. Check the temperature with the
thermometer (Caution - the outlet temperature may be excessively hot).
2. Loosen the Phillips head screw in the TMV knob approximately 6 turns and pull the knob. It should now turn. If not,
loosen the screw a little more until the knob turns.

Advertisement

loading

Summary of Contents for T&S EC-TMV

  • Page 1 EC-TMV & 5EF-TMV Thermostatic Mixing Valve Installation Instructions Models EC-TMV and 5EF-TMV are a direct replacement Thermostatic Mixing Valve (TMV) for the Mechanical Mixing Valve used on ChekPoint (EC) and Equip (5EF) Electronic Faucets. These TMV’s are tested and certifi ed to ASSE 1070. These TMV’s will control and limit the temperature of tempered water to the faucet.
  • Page 2 3. Turn the knob to adjust the outlet water temperature to the desired comfort. It is recommended that the outlet temperature does not exceed 118˚F (48˚C) to reduce the risk of scalding. To decrease the temperature, turn the knob in the direction of the arrow and “C” as marked on the knob ( -->...

This manual is also suitable for:

5ef-tmv