Appendix V. Fan Performance - Carrier 50TCQD17-D24 Service And Maintenance Instructions

Single package heat pump/electric heat
Table of Contents

Advertisement

General Fan Performance Notes:
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories
may add static pressure losses.
4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would
work, Carrier recommends the lower horsepower option.
5. For information on the electrical properties of Carrier's motors, please see the Electrical information section of this
book.
6. For more information on the performance limits of Carrier's motors, please see the Application Data section of this
book.
Table 18. Economizer - - Vertical and Horizontal Duct Configuration
CFM
CFM
Table 19. Electric Heaters - - Vertical and Horizontal Duct Configuration
CFM
25 kW Heater
50 kW Heater
75 kW Heater
CFM
25 kW Heater
50 kW Heater
75 kW Heater

APPENDIX V. FAN PERFORMANCE

Model Sizes 17 and 24
4500
5000
5500
0.047
0.052
0.057
Model Sizes 17 and 24
8500
9000
9500
0.088
0.093
0.098
Model Sizes 17 and 24
4500
5000
5500
0.010
0.010
0.015
0.020
0.020
0.030
0.030
0.040
0.050
Model Sizes 17 and 24
8500
9000
9500
0.045
0.050
0.055
0.090
0.100
0.120
0.140
0.150
0.180
6000
6500
7000
0.062
0.067
0.072
10000
10500
11000
0.103
0.109
0.114
6000
6500
7000
0.020
0.025
0.030
0.040
0.050
0.060
0.060
0.070
0.080
10000
10500
11000
0.060
0.070
0.080
0.130
0.150
0.160
0.200
0.230
0.250
53
7500
8000
0.077
0.082
11500
12000
12500
0.119
0.125
0.131
7500
8000
0.035
0.040
0.070
0.080
0.100
0.120
11500
12000
12500
0.090
0.100
0.105
0.180
0.200
0.230
0.270
0.300
0.330