44
TZIDC, TZIDC-110, TZIDC-120 DIGITAL POSITIONER | CI/TZIDC/110/120-EN REV. E
... 8 Commissioning
... TZIDC
Operating modes
Selection from the operating level
1. Press and hold down MODE.
2. Also press and release rapidly as often as required. The
selected operating mode is displayed.
3. Release MODE.
The position is displayed in % or as a rotation angle.
Operating mode
Mode indicator
1.0
Control mode* with
adaptation of the control
parameters
1.1
Control mode* without
adaptation of the control
parameters
1.2
Manual adjustment** in
the operating range.
Adjust*** using or
1.3
Manual adjustment** in
the measuring range.
Adjust*** using or
*
Since self-optimization in operating mode 1.0 is subject to several factors
during control operation with adaptation, incorrect adjustments could
appear over an extended period.
** Positioning not active.
*** For high-speed mode, press and simultaneously.
TZIDC-110 / TZIDC-120
Commissioning the positioner:
1. Open the pneumatic power supply.
2. Connect fieldbus or power supply to the bus connections.
Position indicator
3. Checking mechanical mounting:
Recommended rotational angle range
Linear actuators
Rotary actuators
Minimum angle
4. Go back to the bus level:
5. Perform standard automatic adjustment in accordance with
6. Set dead zone and tolerance band. This step is only required
Commissioning of the positioner is now complete, and the
device is ready for operation.
The following is now shown in the display:
•
Press and hold down MODE and ENTER; once the
countdown has gone from 3 to 0, release MODE and
ENTER. The device switches to the operating level n
operating mode 1.x.
•
Press and hold MODE and ENTER, and then press or
until operating mode 1.3 (manual adjustment within the
sensor range) is displayed. Release MODE.
•
Press or to move the actuator into the mechanical
end position; check the end positions; rotation angle is
displayed in degrees; for high-speed mode, press or
simultaneously.
•
Press and hold down MODE and ENTER; once the
countdown has gone from 3 to 0, release MODE and
ENTER.
The following is now shown in the display:
Standard automatic adjustment on page 46. Make sure the
device is on the bus level (REMOTE).
for critical (e.g. very small) actuators. In normal cases you can
skip this step.
−28 to 28°
−57 to 57°
25°