Main circuit power supply
200V class: single-phase 200 ~ 240V-50/60Hz
three-phase 200 ~ 230V-50/60Hz
400V class: three-phase 380 ~ 500V-50/60Hz
MCCB(2P)
Power supply
R/L1
1φ200 ~ 240V
Fault detection
-50/60Hz
S/L2
relay
*1 1-phase series don't have T/L3 terminal.
*2 The PO-PA terminals are shorted by
a bar when shipped from the factory.
Before installing the DC reactor (DCL),
remove the bar.
Low-speed
detection signal
DC reactor (DCL)
*2 (option)
P0
MCCB
R/L1
S/L2
Filter
T/L3
*1
Control
circuit
FLC
VF-S9
FLB
FLA
RY
FMV
RC
FMC
CC VIA
FM
Meter
+
Frequency
meter
-
Braking resistor
(option)
PA
PB
PC
U/T1
V/T2
Main circuit
W/T3
P24
F
R
RST
Operation panel
S1
Connector for
common serial
S2
communications
S3
SOURCE
I I
CC
OUT
SINK
Ry
VIB
PP
+
Voltage signal: 0 ~ 10V
-
External potentiometer
(or input voltage signal across
VIA-CC terminals: 0 ~ 10V)
*The VIA terminal and II terminal
cannot be used at the same time.
Motor
IM
Forward
Reverse
Reset
Preset
speed1
Preset
speed2
Preset
speed3
Current signal:
4 ~ 20mA
Designated frequency
attainment signal


Advertisement