Handling; Installations On Appliances That Are Old Or Need To Be Updated - Riello 7200/3F-800 HV PLUS Installation Instructions Manual

Solar storage cylinders
Hide thumbs Also See for RIELLO 7200/3F-800 HV PLUS:
Table of Contents

Advertisement

Riello 7200/3F HV PLUS

8 Handling

The handling of the storage cylinder is carried out with
equipment that is suitable for the weight of the applian-
ce.
To remove the storage cylinder from the pallet, cut the
straps (1). For models 7000/3F 800 HV PLUS - 1000 HV PLUS
and 1500 HV PLUS these can be found under the insulation
near the hinges.
To lift the 7000/3F 800 HV PLUS - 1000 HV PLUS and 1500
HV PLUS storage cylinders, there is a plug (2) with a hole
where a lifting hoop (Ø 10 mm) suitable for the weight of
the tank can be inserted.
To lift the 7000/3F 2000 HV PLUS and 3000 HV PLUS storage
cylinders, after removing the insulation, bind the high
part of the boiler with a cord that can bear the weight
and carefully lift it.
It is possible to dismantle the insulation covering to
make it easier to get through the door of the boiler
room.
Use suitable accident-prevention protections.
It is forbidden to dispose of the packaging material
and keep within children's reach, as it may be a po-
tential source of danger.
9 Installation on appliances that are old or that need to be updated
When the solar storage cylinders 7200/3F HV PLUS are
installed on appliances that are old or that need to be
updated, check that:
- The installation comes with the safety and control com-
ponents in compliance with the specific regulations
- The appliance has been washed, cleaned of mud and
grime, de-aerated and the water seals have been che-
cked
- There is a treatment system for when the supply/make-
up water is particular (the values in the table can be
used as reference values).
7000/3F 800 HV PLUS - 7000/3F 1000 HV PLUS -
7000/3F 1500 HV PLUS
7000/3F 2000 HV PLUS - 7000/3F 3000 HV PLUS
1
REFERENCE VALUES
pH
Electric conductivity
Chlorine ions
Sulphuric acid ions
Total iron
M alkalinity
Total hardness
Sulphur ions
Ammonia ions
Silicon ions
8
2
1
1
6-8
less than 200 mV/cm (25°C)
less than 50 ppm
less than 50 ppm
less than 0.3 ppm
less than 50 ppm
less than 35°F
none
none
less than 30 ppm
3

Advertisement