General Information

The IGSMHS is designed to deliver alarms via the Internet to an AlarmNet central station or
via the AlarmNet-G network, using GSM (Global System for Mobile) technology when the
Internet is not available.
The IGSMHS uses 256 bit AES (Rijndael) encryption which is required for certain
government installations.
You can program a IGSMHS by one of the following methods:
UL

Programming the Control Panel to work with the IGSMHS

For Residential and Commercial control panels, there are certain programming field settings
that must be adhered to for using the IGSMHS. (For programming information, please refer
to the appropriate control panel guides.) Ensure the following programming fields are set:
RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P, and 20P series.)
UL: These control panels have not been evaluated by UL.
Programming Field
29 Menu Mode for IP/GSM Enable
54 Dynamic Signaling Delay
55 Dynamic Signaling Priority
COMMERCIAL Control Panels (Such as the VISTA-128 / 250 series.)
Programming Field
32 Primary Subscriber's Acct No.
56 Dynamic Signaling Delay
57 Dynamic Signaling Priority
58 Comm Central Station #1
59 Comm Central Station #2
#93 Menu Mode
Programming the IGSMHS
The IGSMHS module requires an AlarmNet–I account. For new installations, please obtain
the account information from the central station prior to programming this module. For
replacement installations, the AlarmNet-i account is created automatically when the module is
registered.
Through the AlarmNet Direct website
Through use of a 7720P Programming Tool
Through a programming mode in the control panel, on panels that support this option
Only ECP and Zone Trigger modes have been evaluated by UL.
Category Enable
Category Enable
Setting
1 (Enable LRR.)
0 (Dialer and LRR reports go out at the same time.)
0 (Primary dialer reports first.)
Setting
nnnn (Required for the communicator to report.)
00 (Dialer and LRR reports go out at the same time.)
1 (Communicator, as first reporting.)
111111 (All events will be reported to the primary Central
Station.)
000000 (If Central Station #2 is not used.)
111111 (If Central Station #2 is used.)
Zone programming – set Zone 803 for Type 05.
Device programming – set Address 03 for Type 06 (LRR).
S E C T I O N
3
3-1