Siemens SIMATIC PCS 7 Getting Started page 12

Process control system first steps
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Configuring the hardware and networks
3.1 How to Configure the Hardware
Step
3
4
12
Action
If the hardware catalog is not visible select the View > Catalog command.
Open the "PROFIBUS DP" folder in the hardware catalog.
Open the "ET 200M" folder and select the "IM 153-2" module. Drag-and-drop the
module tot the "DP master system" line.
The "Properties - PROFIBUS interface IM 153-2" opens.
Click "OK".
The program accepts the default settings.
Click on the plus sign to the left of the "IM 153-2" folder in the hardware catalog.
Open the "AI-300" folder. Drag-and-drop the "SM 331 AI8x12Bit" module
(6ES7331-7KF01-0AB0) to
slot 4 at the bottom of the IM 153-2 configuration table.
Close the "AI-300" folder.
Tip:
When the module is selected in the hardware catalog, the Order Number (MLFB) is
displayed below in the information box.
Open the "AO-300" folder. Drag-and-drop the SM 332 AO2x12Bit" module
(6ES7332-5HB01-0AB0) to slot 5 at the bottom of the IM 153-2 configuration table.
Close the "AO-300" folder.
Open the "DI-300" folder. Drag-and-drop the DI16xDC24V" module
(6ES7321-1BH01-0AA0) to slot 6 at the bottom of the IM 153-2 configuration table.
Close the "DI-300" folder.
Open the "DO-300" folder. Drag-and-drop the "SM 322 DO8xDC24V/2A" module
(6ES7322-1BF01-0AA0) to slot 7 at the bottom of the IM 153-2 configuration table.
Close the "DO-300" folder.
First Steps (V7.1)
Getting Started, 03/2009, A5E02122181-01