Commissioning notes
Standards and certificates
Service notes
4/20
Siemens Building Technologies
HVAC Products
When commissioning the plant or when doing maintenance work, make the follow-
ing safety checks:
Safety check
a)
Burner startup with flame detector
darkened
b)
Burner startup with simulated
flame
c)
Burner operation with simulated
loss of flame; for that purpose,
darken the flame detector in op-
eration and leave it in that state
d)
Burner startup with response of air
pressure switch
e)
Burner operation with simulated air
pressure failure
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Directive for gas appliances
- Low-voltage directive
ISO 9001: 2000
ISO 14001: 1996
Cert. 00739
Cert. 38233
Identification code to EN 298
Type
LOK16.140A27*
LOK16.250A27*
LOK16.650A27*
LGK16.122A27*
LGK16.133A27
LGK16.322A27*
LGK16.333A27*
LGK16.335A27*
LGK16.622A27*
LGK16.635A27*
Each time a unit has been replaced, check to ensure that wiring is in an orderly
state. Make the safety check in accordance with section «Commissioning notes»
The KF8832 flame detector current measuring instrument may not be used in con-
tinuous operation
Lockout at the end of «TSA»
Lockout after 40 seconds at the latest
LOK16... with wire link cut: Start
-
repetition followed by lockout at the
end of «TSA»
LGK16... and LOK16... with wire
-
link closed: Immediate lockout
Prevention of startup / lockout during
«t1»
Immediate lockout