Commissioning notes
Standards and certificates
Service notes
4/20
Siemens Building Technologies
HVAC Products
•
When commissioning the plant or when doing maintenance work, make the follow-
ing safety checks:
Safety check
a)
Burner startup with flame detector
darkened
b)
Burner startup with simulated
flame
c)
Burner operation with simulated
loss of flame; for that purpose,
darken the flame detector in op-
eration and leave it in that state
d)
Burner startup with response of air
pressure switch
e)
Burner operation with simulated air
pressure failure
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Directive for gas appliances
- Low-voltage directive
ISO 9001: 2000
ISO 14001: 1996
Cert. 00739
Cert. 38233
Identification code to EN 298
Type
LOK16.140A27*
LOK16.250A27*
LOK16.650A27*
LGK16.122A27*
LGK16.133A27
LGK16.322A27*
LGK16.333A27*
LGK16.335A27*
LGK16.622A27*
LGK16.635A27*
•
Each time a unit has been replaced, check to ensure that wiring is in an orderly
state. Make the safety check in accordance with section «Commissioning notes»
•
The KF8832 flame detector current measuring instrument may not be used in con-
tinuous operation
Lockout at the end of «TSA»
Lockout after 40 seconds at the latest
LOK16... with wire link cut: Start
-
repetition followed by lockout at the
end of «TSA»
LGK16... and LOK16... with wire
-
link closed: Immediate lockout
Prevention of startup / lockout during
«t1»
Immediate lockout