Pairing Mode - Honeywell Limitless WGLA Series Installation And Technical Manual

Wgla limit switch used in conjunction with the limitless wpmm series
Hide thumbs Also See for Limitless WGLA Series:
Table of Contents

Advertisement

Limitless™ WGLA Series

5.3 Pairing Mode

Pairing is required to initiate and establish an RF communication link between each single WGLA and a single
WPMM. The WGLA will be shipped from the factory with two identification labels (1) that are recommended to be
completed and applied to the WGLA housing during the pairing mode. As there are up to 16 WGLAs that can be
paired to a single WPMM, these labels will be used to identify the WGLA switch in the sequence of #1 to #16. The
initial WGLA switch paired to the WPMM will be Sequence #1; the second WGLA paired will be Sequence #2 and so
on. If replacing a WGLA switch that has been purged (see section 6.5 of the WPMM Installation and Technical
Manual), identify the correct replacement Sequence # on the identification labels.
ATTENTION
The operation and LED functions for the WPMM are visually depicted and described in Section 5.4.
This file is also located as a separate file on this CD or at www.honeywell.com/sensing.
ATTENTION
The operation and LED functions for the WPMM are visually depicted and described in Section 5.4.
This file is also located as a separate file on this CD or at www.honeywell.com/sensing.
The battery will need to be activated in the WGLA and proper power applied to the WPMM (green
illuminated) before proceeding with this pairing procedure. Once the pairing is completed, the WGLA selected will
only communicate with the WPMM it was paired to and no other device.
Step
Action
1
Completely read this procedure before starting in order to understand the timing of events that need to be
performed.
2
WGLA: Remove (if required) the two screws
the function button
3
WPMM: Press the Function button
eight seconds at which time the green
function button immediately as it has entered the pairing mode.
4
WGLA: Within a 30 second interval of Step 3, depress the WGLA switch function button
and hold depressed for more than one second and less than 12 seconds at which time the orange
turns on. While in pairing mode, the orange led will flash on for 100 ms every second. The orange
flashes three times 100 ms on, 100 ms off when pairing succeeds. If pairing does not succeed, the orange
LED will turn off and user will need to repeat steps starting with Step 3.
5
WPMM: Successful pairing will be indicated by the green
flash and remaining on for a few seconds before turning off. A short buzzer beep will also occur.
6
To confirm proper pairing between the WGLA and WPMM, actuate the WGLA, and the red LED
illuminate along with a buzzer sound.
7
Record the WGLA Sequence # on identification labels
locations (See Figure 7).
8
Repeat Steps 2-7 to add additional WGLA switches. Up to 16 WGLAs can be paired to a single WPMM.
ATTENTION
The purging of a WGLA per Section 5.4 is required when a previously paired WGLA is desired to be
paired again.
14
Honeywell Sensing and Control
to be used in Step 4.
on WPMM (See Figure 5) for more than four seconds and less than
and amber
on the housing cover (See Figure 4) of the WGLA and locate
LEDs will be flashing which indicates to release the
and amber
and apply to the WGLA housing in desired
50051863
Issue 2
LED
(See Figure 6)
LEDs (See Figure 5) ceasing to
LED
LED
should

Advertisement

Table of Contents
loading

Table of Contents