Lennox CBX25UHV Series Installation And Service Procedure page 8

Table of Contents

Advertisement

Table 7. CBX25UHV‐048 Air Handler Performance (0 through 0.80 in. w.g. External Static Pressure Range)
HEAT Speed
ADJUST
1
2
Jumper
cfm
cfm
Setting
+
1450
1670
NORM
1340
1520
-
1210
1390
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
. . . . . . . .
First-stage cooling air volume is approximately 70% of the second-stage COOL speed setting.
. . . . . . . .
Continuous fan speed is approximately 50% of second-stage COOL speed setting.
®
. . . . . . . .
Lennox Harmony III
Zone Control Applications - Minimum air handler speed is approximately 450 cfm.
Table 8. CBX25UHV‐060 Air Handler Performance (0 through 0.80 in. w.g. External Static Pressure Range)
HEAT Speed
ADJUST
1
2
Jumper
Setting
cfm
cfm
+
1700
1930
NORM
1570
1760
-
1420
1595
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
. . . . . . . .
First-stage cooling air volume is approximately 70% of the second-stage COOL speed setting.
. . . . . . . .
Continuous fan speed is approximately 50% of second-stage COOL speed setting.
®
. . . . . . . .
Lennox Harmony III
Zone Control Applications - Minimum air handler speed is approximately 450 cfm.
Table 9. CBX25UHV, Thermostat and Single-Stage Outdoor Unit Operating Sequence
Operating Sequence
System
Step
Condition
NO CALL FOR DEHUMIDIFICATION
Normal
1
Operation
BASIC MODE (only active on a Y1 thermostat demand)
Normal
1
Operation
Dehumidification
2
Call
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal
1
Operation
Dehumidification
2
call
Dehumidification
1
call ONLY
Jumpers at indoor unit with a single stage outdoor unit
With Condensing unit - Y1 to Y2 and R to O
With Heat Pump - Y1 to Y2
* During dehumidification, cooling air handler speed is as follows: 70% of second-stage COOL cfm for 018, 024, 030, 65% for 036 and 60% for 042, 048 and
060 units.
** Thermostat will maintain the room temperature up to 2°F (1.2°C) cooler than the room thermostat setting in precision mode.
3
4
cfm
cfm
cfm
1880
2340
1050
1730
2100
950
1570
1915
850
3
4
cfm
cfm
cfm
2120
2275
1225
1925
2100
1120
1760
1920
1015
System Demand
Thermostat Demand
Y1
Y2
O
G
W1
W2
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
BDC3 Jumper Speed Positions
First-Stage COOL Speed
1
2
3
cfm
cfm
1200
1340
1200
1230
1000
1100
BDC3 Jumper Speed Positions
First-Stage COOL Speed
1
2
3
cfm
cfm
1410
1530
1260
1400
1160
1275
Relative Humidity
Status
D
Acceptable
24 VAC
Acceptable
24 VAC
Demand
0 VAC
Acceptable
24 VAC
Demand
0 VAC
Demand
0 VAC
Page 8
Second-Stage COOL Speed
4
1
2
cfm
cfm
cfm
1650
1440
1670
1520
1325
1530
1375
1200
1380
Second-Stage COOL Speed
4
1
2
cfm
cfm
cfm
1690
1720
1930
1540
1580
1765
1390
1430
1625
System Response
Air
Com­
Handler
Comments
pressor
CFM
(COOL)
Compressor and indoor
High
100%
air handler follow thermo­
stat demand.
High
100%
Thermostat energizes Y1
and de-energizes D on a
60%/65
call for dehumidification.
High
70%*
High
100%
Dehumidification mode
begins when humidity is
60%/65%
greater than set point.
High
70%*
60%/65%
Thermostat will try to
High
70%*
maintain room humidity
setpoint by allowing the
room space to maintain a
cooler room thermostat
setpoint.**
3
4
cfm
cfm
1950
2340
1740
2150
1600
1950
3
4
cfm
cfm
2140
2270
1970
2100
1780
1890