Powerware PowerPass 9125 User Manual

Distribution module pdm, for use with two-in-one 5000/6000 va
Hide thumbs Also See for PowerPass 9125:

Advertisement

Quick Links

www.powerware.com
9125
For use with Two-in-One
5000/6000 VA Models
PowerPass
Distribution
R
®
Module (PDM)
USER'S GUIDE

Advertisement

Table of Contents
loading

Summary of Contents for Powerware PowerPass 9125

  • Page 1 9125 PowerPass Distribution ® Module (PDM) USER’S GUIDE For use with Two-in-One 5000/6000 VA Models www.powerware.com...
  • Page 3 9125 PowerPass Distribution ® Module (PDM) USER’S GUIDE For use with Two-in-One 5000/6000 VA Models www.powerware.com...
  • Page 4 Powerware and PowerPass are registered trademarks of Powerware Corporation. Greenlee is a registered trademark of Greenlee Textron. ECopyright 2003–2004 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware...
  • Page 5: Table Of Contents

    ........Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 6 Table of Contents Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 7: Introduction

    Chapter 1 Introduction The PowerPass Distribution Module (PDM) is designed to operate with a ® 5000/6000 VA Powerware 9125 uninterruptible power system (UPS). The ® PDM allows you to: Replace or upgrade the UPS without losing power to the protected equipment (see “Using Maintenance Bypass”...
  • Page 8 UPS in een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%). Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 9 Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi). PDM-järjestelmissä kiintealla asennuksella: kuormana olevien laitteiden ylivirtasuojaus ja erotuskytkimet tulee toteuttaa kuormapiireissa. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 10 Pour les models PDM ayant des sorties câblées, les interrupteurs de déconnexion convenables pour le(s) circuit(s) de sortie de courant alternatif doivent être fournie par un autre fournisseur. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 11 La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max). Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 12 A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%). Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 13 контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40 ° С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%). Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 14 Para los sistemas PDM con salidas cableadas permanentemente, los interruptores de desconexión debidamente clasificados para el/los circuito(s) de CA de salida serán suministrados por terceros. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 15 Överströmsskydd för de utgående växelströmskretsarna ska tillhandahållas av andra för PDM-system med fasta utgångar. Bortkopplingsswitchar med passande dimensionering för de utgående växelströmskretsarna ska tillhandahållas av andra för PDM-system med fasta utgångar. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 16 Introduction Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 17: Installation

    Unplug the UPS; the UPS shuts down in five seconds. The bar graph and battery indicators flash briefly prior to shutdown. Disconnect the power cord from the UPS input connector. Disconnect the protected equipment power cord from the UPS. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 18: Ups Setup

    Installation UPS Setup The Powerware 9125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, follow the instructions with the rail kit to set up the UPS. Otherwise, continue to the following section “Installing the Internal Batteries”...
  • Page 19 If the UPS is in a rack and you are installing an optional Extended Battery Module (EBM), continue to “EBM Installation” on page 16; otherwise, continue to “Plug-Receptacle PDM Installation” on page 17 or “Hardwired PDM Installation” on page 23. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 20: Tower Setup

    UPS and EBM) as shown in Figure 4. Figure 4. Tower PDM Configuration Align each joining bracket with the adjacent cabinet screw holes and secure with the supplied screws (see Figure 5). Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 21 If you are installing an optional EBM, continue to the following section, “EBM Installation;” otherwise, continue to “Plug-Receptacle PDM Installation” on page 17 or “Hardwired PDM Installation” on page 23. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 22: Ebm Installation

    Installation” or “Hardwired PDM Installation” on page 23. Battery Circuit Breaker UPS Battery Connector EBM Cable Battery Circuit EBM Battery Breaker Connector Figure 6. Typical EBM with PDM Installation Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 23: Plug-Receptacle Pdm Installation

    In most applications, the voltage switch does NOT need changing. To change the switch position, remove the bracket screw and turn the switch. Flip the bracket around to fit the new position and reinstall. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 24 PPDM L6-30&L14-30 Models PDM Output Voltage Input Voltage Input Voltage 208V Switch Position Default 240V Switch Position (from UPS) (L6-30R/L14-30R/5-15R) (L6-30R/L14-30R/5-15R) 208/240/120 208/208/104 220/252/126 220/220/110 230/262/131 230/230/115 240/272/136 240/240/120 Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 25 PDM rear panel. Plug the UPS power cord into an L6-30 power outlet. µ indicator flashes, indicating the UPS is in Standby mode with the equipment offline. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 26 NOTE The batteries charge to 80% capacity in less than 2 hours. However, it is recommended that the batteries charge for 24 hours after installation or long-term storage. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 27: Remote Emergency Power-Off

    Installation Remote Emergency Power-Off The Powerware 9125 includes a REPO connector that allows power to be switched off at the UPS output receptacles from a customer-supplied switch in a remote location. The REPO feature shuts down the protected equipment immediately,...
  • Page 28 Plug in the UPS and start the UPS by pressing the On button. Activate the external REPO switch to test the REPO function. De-activate the external REPO switch and restart the UPS. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 29: Hardwired Pdm Installation

    Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty. The Powerware 9125 requires a dedicated branch circuit that meets the following requirements: 40A minimum circuit with short circuit and overcurrent protection 200–240 Vac...
  • Page 30 In most applications, the voltage switch does NOT need changing. To change the switch position, remove the bracket screw and turn the switch. Flip the bracket around to fit the new position and reinstall. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 31 Insert each conduit through a wiring access entry and attach the conduit fitting to the panel. Strip 0.35I (9 mm) of insulation from the end of each incoming wire. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 32 Output Neutral Input L2/N Output Line 1, 230–240V Output Line 2/N, 230 – 240V Input L1 Output Input Earthing Earthing Figure 12. PPDM EURO HW Model Terminal Block Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 33 Replace the wiring access cover and the conduit landing plate. Plug the input and output cords of the PDM into the input and output power connectors on the UPS rear panel. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 34 NOTE The batteries charge to 80% capacity in less than 2 hours. However, it is recommended that the batteries charge for 24 hours after installation or long-term storage. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 35: Pdm Rear Panels

    PDM Input Cord (to UPS) PDM Output Cord (to UPS) PDM Output Circuit Breaker Input Connector Output Receptacles (Eight 5-15R) Output Receptacle (L5-30) Neutral-to-Ground Bonding Screw Figure 16. PPDM L5-30 Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 36 PDM Output Cord (to UPS) Output Receptacle (L6-30) PDM Output Circuit Breaker Input Connector Output Receptacles (Four 5-15R) Output Receptacle (L14-30) Neutral-to-Ground Bonding Screw Figure 18. PPDM L6-30&L14-30 Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 37: Configuration

    If you press the On button and nothing happens, the UPS is still in Operation mode. Repeat Step 1 to enter Configuration mode, and then perform Step 2. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 38 Configuration and Operation mode. Test/Alarm On Button Reset Button Press the On button to scroll to the next option. Figure 19. Using the Configuration Mode Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 39 Flashing Alarm DOES NOT sound when the polarity of the (default) outlet is reversed or the ground connection is missing. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 40 Configuration Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 41: Operation

    Disconnect the PDM input and output cords from the UPS. See Figure 8 on page 19. The UPS shuts down in five seconds. The bar graph and battery indicators flash briefly prior to shutdown. Remove the UPS. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 42 The bar graph indicators display the percentage of load being applied to the UPS. The UPS is now in Normal mode and supplying power to your equipment. Reinstall the PDM front panel. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 43: Specifications

    EMC (Class A) EN 50091-2, FCC Part 15, ICES-003 Dimensions (WxDxH) 17.4” x 26.9” x 5.1” (3U) (44.2 x 68.3 x 13 cm) Weight 103 lb (46.7 kg) Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 44 Specifications Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 45: Pdm Schematics

    Chapter 6 PDM Schematics This section shows the schematics of each PDM model. Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 46 PDM Schematics Figure 20. PPDM L6-30 Schematic Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 47 PDM Schematics Figure 21. PPDM L6-20 Schematic Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 48 PDM Schematics Figure 22. PPDM L5-30 Schematic Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 49 PDM Schematics Figure 23. PPDM L14-30 Schematic Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 50 PDM Schematics Figure 24. PPDM L6-30&L14-30 Schematic Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 51 PDM Schematics Figure 25. PPDM EURO HW Schematic Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 52 PDM Schematics Figure 26. PPDM HW Schematic Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 53: Service And Support

    A replacement or repair unit will be shipped, freight prepaid for all warrantied units. NOTE For critical applications, immediate replacement may be available. Call the for the dealer or distributor nearest you. Help Desk Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...
  • Page 54 Service and Support Powerware 9125 Two-in-One (5000/6000 VA) PDM User’s Guide Rev B www.powerware.com ®...