Jøtul NVI 2000 Installation Manual

Chimneysystem

Advertisement

INSTALLATION GUIDE
NVI 2000 Chimneysystem
23.06.2017 | JAN - 2019
MARKEDETS SIKRESTE STÅLPIPE
THE SAFEST CHIMNEY ON THE MARKET

Advertisement

Table of Contents
loading

Summary of Contents for Jøtul NVI 2000

  • Page 1 INSTALLATION GUIDE NVI 2000 Chimneysystem 23.06.2017 | JAN - 2019 MARKEDETS SIKRESTE STÅLPIPE THE SAFEST CHIMNEY ON THE MARKET...
  • Page 3: Table Of Contents

    Extra cladding pipe, Combi Roof through-connection, Combi Warranty provisions Roof hood, Combi Through-connection Roof hood, installation Cover plate, installation Technical specifications Performance declaration, NVI 2000 Climbing arrangements Rain collar Wall bracket, installation Rain/top protection Advice and provisions Laterally offset chimney Chimney length, adaptation Maintenance guidelines Jøtul Chimney system...
  • Page 4: Advice And Provisions

    ADVICE AND PROVISIONS Advice and provisions General This installation guide describe how to install, commission and maintain your Jøtul pipe. You should keep the installation guide, both to show to the local fire/chimney sweep authority at the time of the first inspection, and for subsequent fire safety checks that are performed at regular intervals. It is impor- tant for you to fill out the relevant details on page 36 of this installation guide.
  • Page 5 Lateral offset of NVI 2000 NVI 2000 can be offset laterally to an angle of between 15° - 90°. If the pipe bend i greater than 45°, i.e. 46° - 90°, the cleaning hatch(es) must be positioned in order to facilitate chimney sweeping of the first vertical sec- tion from the fireplace as well as the diagonal section between the bends.
  • Page 6: Technical Specifications

    TECHNICAL SPECIFICATIONS Technical specifications SAFETY RESISTANCE TO THE NEAREST FLAMMABLE MATERIALS MAXIMUM LOAD ON THE CHIMNEY ELEMENT All dimensions = 13 kN VERTICAL HORIZONTAL (MM) (MM) Fully insulated modules PRESSURE DROP Semi-insulated modules Pressure drop in bends and bend connections 90° = 1.12 Uninsulated modules HEAT RESISTANCE...
  • Page 7: Getting Started

    NVI20151000 & NVI20151001 must be indicated on the label. SS EN 1856-1 Flerväggig systemskorsten av metall NVI 2000 & NVI 2000 Combi: SS EN 1856-1:2009 T450-N1-D/W-V2-L50100-G50 Tryckhållfasthet: Maximalt 20 m skorstenssektioner Flödesmotstånd: 0,15µm Using the fireplace for the first time Värmemotstånd: 0,40 m²K/W vid T450...
  • Page 8: Maintenance And Servicing

    Operation The NVI 2000 system chimney is designed to cope with flue gas temperatures of up to 450°C and a fireplace output of max. 120 kW in the case of continuous operation. Ignoring these values through the use of different combustion methods, fuels and fuel quantities can lead to serious damage to the fireplace and, in the worst...
  • Page 9 INSTALLATION METHOD Choice of installation method for chimneys Connected at top Connected at top Connected at rear Connected at rear Semi-insulated Fully insulated Semi-insulated Fully insulated Connected at top Connected at rear Connected at rear Connected at rear Uninsulated Uninsulated through inner wall through outer wall Jøtul Chimney system...
  • Page 10 NVI 2000 STRUCTURE AND PARTS Structure of the chimney and component names Curved rain guard Rain protector piece Telescopic section Rain protector piece Stay plate Rain protection Rain collar Casing Roof seal Stay plate Diffusion barrier Lower fitting Locking band Bottom fitting...
  • Page 11: Standard Installation, Nvi2000

    NVI 2000 STANDARD INSTALLATION Standard assembly, internal Insulated modules The chimney is installed from the bottom up. Start by measuring the hole in the ceiling based on the fireplace’s flue connecting piece. Cut out the hole in the ceiling to ensure the correct safety distance to...
  • Page 12 NVI 2000 - REAR CONNECTION Rear connection directly behind the fireplace Start by measuring the distance from the floor to the middle of the fireplace’s rear connecting piece. Install the support leg on the rear connection, adapt the length of the support leg so that the measurement between the floor and the centre is the same as on the...
  • Page 13: Cover Plate, Installation

    NVI 2000 - CEILING RING Installation of cover plate (round/square) Cut a hole in the insulation panel that is supplied with the ceiling plate. The hole must be the same size as the cladding pipe. Cut the panel in half and insert the pieces up into the floor structure around the chimney.
  • Page 14: Through-Connection

    NVI 2000 - THROUGH-CONNECTIONS Through-connections Adapter in flammable floor structure Adapter, semi-insulated to fully insulated module If a semi-insulated module ends up fully or partially in the floor structure, it must be provided with additional insulation with a 30 mm thick, mesh-reinforced mat that...
  • Page 15 NVI 2000 - THROUGH-CONNECTIONS Floor structure with blown insulation Non-flammable material When blown insulation is used in the floor structure, In the case of a through-connection in non-flam- a plate shaft, spiral pipe or similar round pipe mod- mable material of class EI60, no safety distance is ule must be installed with a minimum distance of 5 required.
  • Page 16: Wall Bracket, Installation

    NVI 2000 - WALL BRACKET Through-connection, flammable wall • Mark on the wall the location of the centre of the fireplace’s flue gas output. 50 mm • If the wall is made of non-flammable material, make a hole that is sufficiently large for cladding and a seal against draughts.
  • Page 17 NVI 2000 - WALL BRACKET Wall bracket for rear connection, continued The wall bracket comes with a pre-installed load-bear- ing plate. This distributes the load out towards the stronger edges. The load-bearing plate must be used when installing through an outer wall.
  • Page 18: Roof Hood, Installation

    NVI 2000 - ROOF HOOD Installation of rectangular hood above roof Bottom fitting Check the surface after making a hole in the roof and make sure that the bottom fitting has a load-bearing, stable attachment. If not, build a frame attachment.
  • Page 19 NVI 2000 - ROOF HOOD Lower fitting, steel Roofing tiles Build a frame around the bottom fitting’s connecting piece at the same height as the roofing. Return the cornice and then the roofing. In some cases, it may be necessary to cut roofing tiles.
  • Page 20 NVI 2000 - ROOF HOOD Lower fitting, aluminium membrane for roofing tiles, slates, roofing tile profiles made of steel and roofs made of corrugated plastic Build a frame around the connecting piece at the same height as the roofing. Return the cornice and then the roofing. In some cases, it may be necessary to cut the roofing.
  • Page 21 NVI 2000 - ROOF HOOD Installation of telescopic section and rain protection If the chimney is exposed to a lot The telescopic section is pre-installed with the roof. of wind – position the curved rain guard in the direction of the wind The roof has guides regarding where the curved rain to ensure optimum protection.
  • Page 22 NVI 2000 - ROOF HOOD Installation above roof, round hood, stay plate After making a hole in the roof, inspect the surface and make sure that the stay plate is supplied with a load-bearing, stable attachment. If not, build a frame for attachment.
  • Page 23 NVI 2000 - ROOF HOOD Roof seal Felt roof/Sarnafil Check with the roof producer that it is permitted to make a roof through-connection in the roof in ques- tion. Then follow the producer’s guidelines for the roof through-connection. New roo ng...
  • Page 24 NVI 2000 - ROOF HOOD Metal roof For roofs made of metal, the roof seal must reach up to the roof ridge. If this is not satisfied, extension plates must be used. Loosen the roof ridge plate. Start by installing the enclosed weatherstrip at the bottom edge of the roof seal to prevent moisture being blown in.
  • Page 25: Rain Collar

    NVI 2000 - ROOF HOOD Rain collar Place the vulcanising tape over the roof seal and mod- Module pipe ule pipe in order to seal the gap that arises. The tape must be stretched so that there is pressure around the at least 20 mm entire chimney.
  • Page 26: Chimney Length, Adaptation

    NVI 2000 - ADAPTATION OF MODULE Adaptation of chimney modules When there is a requirement to adapt the length of modules, all components must be cut by the same amount. The adjustable end is the lower part, as illustrated. The rubber ring on the cladding pipe must be re- tained.
  • Page 27: Laterally Offset Chimney

    NVI 2000 - LATERAL OFFSET Installation of laterally offset chimney If the pipe is angled more than 45° from the ver- tical, or if the distance between 15-45° bends is more than 200 cm, a cleaning hatch is required. The max. distance between cleaning hatches is 5 meter.
  • Page 28 NVI 2000 COMBI www.jotul.no...
  • Page 29 Otherwise, the same advice and provisions apply as for NVI 2000. In order for the approval/CE marking to be valid, the NVI 2000 Combi must be used as a supply air pipe and be connected to the fireplace with the enclosed supply air duct.
  • Page 30 NVI 2000 COMBI - STRUCTURE AND PARTS NVI2000 Combi (integrated supply air) structure and designation of parts Rain protector piece Telescopic section Stay plate Rain protector piece Rain top Rain collar Roof seal Casing Stay plate Lower fitting Diffusion barrier Locking band Bottom fitting...
  • Page 31: Connection Duct, Combi

    NVI 2000 COMBI - STANDARD INSULATION Installation of NVI2000 COMBI Internal installation Start the installation with the connecting piece, install the rectangular connecting piece in the direction in which the connection duct is subsequently to be installed. If there is a difference between the fireplace’s flue pipe and the chimney, use a suitable adapter.
  • Page 32: Roof Through-Connection, Combi

    NVI 2000 COMBI - THROUGH-CONNECTION Roof through-connection, adapter, semi to fully insulated If a semi-insulated module ends up fully or partially in the joisting, it must be provided with additional insulation with a 30 mm thick, mesh-reinforced mat Nettarmert matte Mesh-reinforced mat that comes with the adapter.
  • Page 33: Roof Hood, Combi

    NVI 2000 COMBI - ROOF HOOD Rain/top protection around hood When adapting the chimney length, it is important to ensure that the supply air is able to pass freely through the top of the chimney. Leave a distance of at least 30 mm between the roof and the end of the cladding pipe.
  • Page 34: Extra Cladding Pipe, Combi

    NVI 2000 COMBI - ROOF HOOD Extra cladding pipe for round hood An extra cladding pipe with a dimension of Ø275 is supplied with the delivery of NVI2000 Combi when a round chimney hood is selected. The function of the pipe is to minimise the risk of condensation.
  • Page 35: Warranty Provisions

    25-year warranty The NVI 2000 chimney system is made from materials of the highest quality, which means we can guaran- tee that the NVI 2000 has a long service when handled correctly and when our installation guide has been followed.
  • Page 36 CHECKLIST/INSTALLATION REPORT Checklist and confirmation of completed inspection of chimney installation Address of the property: Address Post code Town/city Owner’s name Installer (company) Name Address Post code Town/city Chimney’s designation: Type of chimney Dimensions No. of fireplaces connected to the chimney Height of chimney Offset Roofing...
  • Page 37 CHECKLIST/INSTALLATION REPORT A confirmation of the inspection of the installation is a precondition for the chimney being able to be used. The existence of such a confirmation is also essential for Jøtul’s warranty for the product. Ensure that this page is filled out and that a copy is sent to the local authority’s chimney sweep service.
  • Page 38 NVI 2000 - ANGLE TABLE 125-190 Angles and measurements for the dimensions Ø125 - Ø190 D = 165 mm for all bends. Description of measurements Renslucka Cleaning hatch B mm placering 2 location 2 D = 165 mm for all bends...
  • Page 39 NVI 2000 - ANGLE TABLE Angles and measurements for the dimensions Ø250 D = 275 mm for all bends. Description of measurements D = 275 mm for all bends Angle 90°, three segments Structure dimension A = 350 mm Angle 15°...
  • Page 40 NVI20151000 & NVI20151001 System för bedömning och fortlöpande kontroll av prestanda: SS EN 1856-1 Flerväggig systemskorsten av metall NVI 2000 & NVI 2000 Combi: SS EN 1856-1:2009 T450-N1-D/W-V2-L50100-G50 Tryckhållfasthet: Maximalt 20 m skorstenssektioner Flödesmotstånd: 0,15µm Harmoniserad standard: Värmemotstånd: 0,40 m²K/W vid T450 Resistens mot soteld: Godkänd...
  • Page 41 Nr: DOPSE-T450-CPR-265403 Produkttypens identifi kationskod: Flerväggig systemskorsten av metall, modell NVI 2000 COMBI: T450 – N1 – D/W – V2 – L50100 – G50 Avsedd användning: Skorsten för att leda bort rökgaser från eldstäder som eldas med ved, pellets, lättolja, gas, torv och kol som avger maximal effekt 120kW och maximal rökgastemperatur 450ºC.
  • Page 42 Produkttyp: Flerväggig systemskorsten av metall. Typ enligt standard: NVI 2000: SS EN 1856-1:2009 T600-N1-D/W-V2-L50100-G50 Avsedd användning: Skorsten för att leda bort rökgaser från eldstäder som eldas med ved, pellets, lättolja, gas och torv som avger maximal effekt 120kW och maximal rökgastemperatur 600ºC.
  • Page 44 Jøtul AS Follow us on Facebook - www.facebook.com/jotulint Postboks 1411 1602 FREDRIKSTAD Jøtul continuously strives to improve its products and E-mail: stålpipe@jotul.no reserves the right to modify specifications, colours and fittings without prior notice. www.jotul.no MARKEDETS SIKRESTE STÅLPIPE THE SAFEST CHIMNEY ON THE MARKET...