5. Technical data
INSULATION VOLTAGE
AMBIENT TEMPERATURE
STORAGE TEMPERATURE
HUMIDITY CLASS acc. to DIN 40040
DEGREE OF PROTECTION acc. to DIN 40050IP00
MECHANICAL STRESSING
MOUNTING SYSTEM
DIMENSIONS
WEIGHT
Supply voltage (V v )
(DC voltage)
-Nominal value
-Permissible range
-Briefly
Current drain (nominal value)
8 inputs:
-Input voltage
for "1" signal
for "0" signal
-Input current (1 signal)
8 outputs:
-Output voltage
for "1" signal
for "0" signal
-Output current
for "1" signal
-Residual output current
for "0" signal
-Continuous short-circuit current
Siemens AG Dk-Nr. 283641
SIMADYN D Hardware User Manual
acc. to VDE 0160/Draft, came into force 12/90
Electrical isolation:
- between inputs and outputs
- between input circuits
0 to 55 o C
-40 to 70 o C
F
acc. to SN 29010 Class 12
Can be snapped onto mounting rails
118mm*135mm*42mm
approx. 320g
SIMADYN D side
24V
20V to 30V
1.5*V rated
Duration 0.5s
90mA
(U v - 3)V
0 to +3V
max. 10mA
max. 4uA
max. 17mA
Edition 05.95
System side at
24V
24V
20V to 30V
1.5*V rated
Duration 0.5s
50mA
+13V to +30V
-3V to +6V
or input open-circuit
6mA
Technical data
System side at
48V
48V
40V to 60V
1.5*V rated
Duration 0.5s
50mA
+26V to +60V
-3V to +12V
or input open-circuit
6mA
5