Connecting The Mains Supply; Connecting The Ambient Thermostat - Baxi Fourtech Series Operating And Installation Instructions

High performance gas-fired wall-mounted boilers
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 36
IMPORTANT:
if fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the duct
passes through building walls. For detailed installation instructions, consult the technical data provided with the accesso-
ries.
17. ELECTRICAL CONNECTIONS
This machine is only electrically safe if it is correctly connected to an efficient earth system in compliance with current
safety regulations.
Connect the boiler to a 230V single-phase earthed power supply using the supplied three-pin cable, observing correct
LIVE-NEUTRAL polarity.
Use a double-pole switch with a contact separation of at least 3 mm.
When replacing the power supply cable, fit a harmonised HAR H05 VV-F' 3x0.75mm2 cable with a maximum diameter
of 8 mm.
...Access to the power supply terminal block
The 2A fast-blowing fuse is incorporated in the power supply terminal block (to check and/or replace the fuse, pull out
the black fuse carrier).
IMPORTANT: respect polarity L (LIVE) - N (NEUTRAL).
(L) = Live (brown)
(N) = Neutral (blue)
= Earth (yellow-green)
(1) (2) = Contact for ambient thermostat
Figure 9
18. CONNECTING THE ROOM THERMOSTAT
INSTRUCTIONS FOR FITTERS
926.116.5 - en
49