Manual call point
Hide thumbs Also See for FDM223-Ex:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
IECEx:
94/9/EWG:
(ATEX-directive)
Ex-related connection data,
intrinsically safe:
Line to external alarm
indicator:
0786
14
0102
FDM223-Ex - Manual callpoint for use in fire detection and fire alarm systems installed in buildings.
305/2011/EU (CPR): EN 54-11 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581 ;
The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC), which is
obtainable via the Customer Support Center: Tel. +49 89 9221-8000 or http://siemens.com/bt/download
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 – 724 24 24
www.siemens.com/buildingtechnologies
A6V10349619_h_--_--
Ex ia IIC T4 Ga, Ta = -35...70 °C
Ex ia IIIB T135 °C Da, Ta = -35...70 °C
II 1 G Ex ia IIC T4 Ga, Ta = -35...70 °C
II 1 D Ex ia IIIB T135 °C Da, Ta = -35...70 °C
U
i
I
i
P
i
L
i
C
i
Operating current (quiescent)
U
0
I
0
P
0
L
0
C
0
Only for connecting passive, external alarm indicators with negligibly low inductance and
capacitance levels.
FDM223-Ex
2014/34/EU (ATEX): EN 60079-0 / EN 60079-11 / EN 60079-26
DoP No.: 0786-CPR-21320; DoC No.: CED-FDM223-Ex
Technical specifications and availability subject to change without notice.
SAP order no. A5Q00054045
28 V
92 mA
650 mW
Negligible
0.2 nF
200 µA
14.2 V
480 mA
195 mW
100 µH
38 nF
Siemens Schweiz AG; Theilerstrasse 1a
CH-6300 Zug
Technical data: see doc. A6V10349616
© Siemens Switzerland Ltd, 2012