10.4 Technical data DALI

Transmission medium (bus cable)
Baud rate
Bus line polarity
Bus terminating resistor
The communication signal (information) is transferred symmetrically, i.e., as
voltage difference between the two bus lines (and not as a voltage difference to the
earthing potential). The sign preceding the voltage between DA+ and DA–
determines signal values 0 and 1.
Cable type
Wiring cross section
Distance (sum of all bus sections)
Screens
PXC3... devices do not have a connection for bus cable screens.
Bus power through the PXC3... room automation
station
Mounting and installation
DALI network
TP (twisted pair)
1.2 kbps
DA, DA (interchangeable)
Not required
2-wire, stranded (
or
5-wire, stranded
or
7-wire, stranded
2
Min. 1.5 mm
(AWG16).
Max. 300 m
Not required
DC 16 V, 128 mA.
(for max. 64 DALI devices)
one wire pair)