Operation

Intended use
The RE8ST Testifire 1001-045 ST test kit is a tool for
checking the function of smoke and heat detectors. To run
this check, a heating element is heated in a tester until the
heat detector being checked issues an alarm.
Smoke detectors are tested by setting off a smoke capsule in
the tester.
The following modules form part of the RE8ST test kit:
· 1x Testifire 1001-045 tester
· 2x RE7T-B1 Solo770 rechargeable batteries for the
tester
· 1x RE-8S smoke capsule
· 1x RE7T-C1 Solo727 charger for rechargeable
battery
· 2x mains cable for charger RE7T-C1 Solo727
· 1x Quick Start User Guide
· 1x Installation Instructions RE8ST and RE8STCO
(this document)
The RE8STCO Testifire 2001-045 STCO test kit is a tool for
checking the function of smoke, heat, and CO detectors. To
run this check, a heating element is heated in a tester until
the heat detector being checked issues an alarm.
Smoke detectors are tested by setting off a smoke capsule in
the tester.
CO detectors are tested by setting off a CO capsule in the
tester.
The following modules form part of the RE8STCO test kit:
· 1x Testifire 2001-045 tester
· 2x RE7T-B1 Solo770 rechargeable batteries for the
tester
· 1x RE8-S smoke capsule
· 1x RE8-CO CO capsule
· 1x RE7T-C1 Solo727 charger for rechargeable
battery
· 2x mains cable for charger RE7T-C1 Solo727
· 1x Quick Start User Guide
· 1x Installation Instructions RE8ST and RE8STCO
(this document)
2
Building Technologies
Fire Safety
WARNING
Use of the RE8ST and RE8STCO test kits in
electrical switching stations or areas where there is
a danger of explosion.
Danger to life
·
Do not use the RE8ST and RE8STCO test kits in
electrical switching stations or areas where there
is a danger of explosion.
CAUTION
Falling objects
Risk of injury
·
Wear a hardhat when working with telescope
rods.
Installing FDUM29x telescope rods (Fig. 1)
Insert the rechargeable battery (2) into the tester (1).
1.
Fit the Solo719 adaptor RE7T-A (3) on the rechargeable
2.
battery (2).
Fit a FDUM29x telescope rod (4) on the Solo719 adapter
3.
RE7T-A (3).
Additional information
In the Quick Start Guide from No Climb Products Ltd.
supplied with the test kit, you will find information on the
following topics:
· Safety information for operating the test kit
· Operation of the test kit
· Procedure for testing detectors
· Replacing capsules
· Replacing and charging the rechargeable battery
You can download the detailed User Manual for the
test kits from: www.testifire.com.
A6V10387053_e_--_--
2018-05-31

Advertisement

loading

This manual is also suitable for:

Re8stco testifire 2001-045 stco