Troubleshooting - Blodgett KTT-G Series Installation Operation & Maintenance

Gas table top tilting kettle
Table of Contents

Advertisement

SYMPTOM
Spark is present but the pilot
will not light.
Pilot lights, but main burner
will not come on and spark
does not stay on.
Pilot lights, but main burner
will not come on, the spark
stays on.
Main burner comes on but
will not stay on.
22
OM-KTT/KTC-G
WHO
Auth Service
a. That the pilot valve is securely connected to terminals.X
Rep Only
b. For 24 VAC at terminals PV and PV/MV. If 24V is not present,
replace the ignition control module.X
b. That gas pressure is at least 3.5" W.C.(8.7818 b).X
c. For gas at the pilot. If it is not flowing:
(1) Check the pilot gas line for kinks and obstructions.X
(2) Clean orifice, if necessary.X
(3) Check magnetic operator for pilot valve on gas valve. Repair
or replace as necessary.X
d. That the pilot spark gap is located in the pilot gas stream. If
not, adjust or replace the pilot burner.X
e. For drafts. Shield the pilot burner, if necessary.X
Auth Service
a. For 24 V between terminals PV and PV/MV. If 24V is not
Rep Only
present, replace the ignition control module.X
b. That gas pressure is at least 3.5" W.C.(8.7818 b).X
c. Electrical connections of the main valve to terminals, to a sure
that they are securely attached. Check magnetic operator for
pilot valve on gas valve. Repair or replace as necessary.X
Auth Service
a. Check for bad burner ground. If necessary, repair with high
Rep Only
temperature wire.X
b. Pilot burner ceramic insulator for cracks.X
c. That cable is not grounded out. If it is, correct the ground-out
condition or replace cable.X
d. For proper gas pressure.X
e. Clean pilot assembly, or replace if necessary.X
f. Tighten all mechanical and electrical connections.X
g. If the pilot flame is weak, increase pilot orifice size.X
h. Replace ignition control module.X
Auth Service
a. Check burner ground for bad wire or connection. Replace if
Rep Only
necessary with high temperature wire.X
b. Check for low gas supply pressure. If necessary, replace
ignition control module.X

Troubleshooting

WHAT TO CHECK
X indicates items which must be performed by an authorized technician.