2. Modify the administrator password.
Enter a new password in the "New Administrator Password" and "Confirm" input boxes.
For information on the passwords set in the factory, refer to the operating instructions, section "Security settings and user
roles".
Note
Use caution when changing the administrator password. If the administrator password is lost, you will not be able to
operate the IE/WSN-PA Link from the administrator role.
3. Click the "Submit" button.
4.2.5

Network data

1. Select the "Setup" > "Network" > "Settings" menu command.
The "Network Settings" dialog opens.
2. Enter the network ID of your WirelessHART network in the "Network ID" input box. Numbers in the range 0 to 65535 are
permitted.
3. Enter the join key of your WirelessHART network in the "Join key" input box as a hexadecimal number.
4. Click the "Submit" button.
5. Select the "Setup" > "Restart Apps" menu command.
This completes the initial commissioning of the IE/WSN-PA Link. You can remove the PC/laptop and restore the original
settings on the PC/laptop.
4.2.6

Project engineering

Project engineering
You will find detailed instructions of all configuration functions of the Link in the operating instructions (PDF) of the IE/WSN-
PA Link.
4.3
Commissioning and operating redundant Links
Requirements for the redundancy function
● 2 Links with order number 6GK1 411-6CA40-0BA0
(Device variant with connector for an external antenna)
The two Links must meet the following requirements:
Identical hardware product version
Identical firmware version (at least version 4.3.17)
IE/WSN-PA Link
A5E02509264-AE, 01/2015