Troubleshooting for Error Code

Code
Description
No.
1
Problem in remote room air sensor
2
Problem in refrigerant (inlet side) sensor
6
Problem in refrigerant (outlet side) sensor
8
Problem in water tank sensor
16
Problems in sensors
17
Problem in water-inlet sensor
18
Problem in water-outlet sensor
19
Problem in water-interim sensor
Bad communication between remote
3
controller and unit.
Bad communication between Main PCB
5
assembly(Heater) and Main PCB
assembly(Inverter) of the unit.
53
9
PCB program (EEPROM) fault
14
Problem in flow switch
15
Water pipe overheated
20
Thermal fuse is damaged
Check Points, Maintenance and Troubleshooting
Cause
• Incorrect connection between
sensor and PCB(Heater).
• PCB(Heater) fault
• Sensor fault
• Incorrect connection between
sensor and PCB(Heater)
• PCB(Heater) fault
• Sensor fault
• The connector for transmission is
disconnected
• The connecting wires are
misconnected
• The communication line is broken
• Main PCB assembly(Inverter) is
abnormal
• Main PCB assembly(Heater) is
abnormal
• Electrical or mechanical damage a
the EEPROM
• Flow switch is open while internal
water pump is working
• Flow switch is closed while internal
water pump is not working
• Flow switch is open while DIP
switch No. 5 of Main PCB
assembly(Heater) is set as on
• Abnormal operation of electric
heater
• Leaving water temperature is
above 57 ℃
• Thermal fuse is cut off by
abnormal overheating of internal
electric heater
• Mechanical fault at thermal fuse
• Wire is damaged
Normal Condition
• Resistance: 10 kΩ at 25
centigrade (unplugged) → for
Remote room air sensor
• Resistance: 5 kΩ at 25 centigrade
(unplugged) → for all sensors
EXCEPT remote room air sensor
• Voltage: 2.5 V DC at 25 centigrade
(plugged) (for all sensors)
• Refer resistance-temperature table
to check in different temperature
• Wire connection between remote
controller and Main PCB
assembly(Heater) should be tight
• Output voltage of PCB should be
12 V DC
• Wire connection between remote
control panel and Main PCB
assembly(Heater) should be tight.
• This error can not be permitted
• Flow switch should be closed while
internal water pump is working or
DIP switch No. 5 of Main PCB
assembly(Heater) is set as on
• Flow switch should be open while
internal water pump is not working
• If there is no problem in electric
heater control, possible maximum
leaving water temperature is 57 ℃
• This error will not be happened if
temperature of electric heater tank
is below 80 ℃
Installation Manual 95