Use
Operating lines
Caution
Notes
Use
24/52
Building Technologies
HVAC Products
Status messages
Sorted
Deleted
Sorted
6.3.1

Submenu "Create list"

• When the bus operator unit is connected to plant for the first time
• When the bus operator unit is connected to plant as a service unit
Main menu > Commissioning > Device list > Create list
Operating line
Area
Line
Start search
Number of devices current
A search is made in the network for operable Synco™ devices in accordance with the
parameters set. An existing device list will first be deleted. The search for devices is
only possible within the selected area. Settings Area and Line confine the search for bus
users to the required part of the network. This also reduces the time required for the
search to a reasonable level.
*
" for the line, the search covers all lines of the required area. In
When using setting "
that case, the search lasts about 15 minutes and cannot be aborted.
The device search is started via operating line Start search.
The number of devices found is displayed by the value of Number of devices current.
When creating the device list, all existing devices, device names and favorite
pages will be deleted!
• The device list can comprise a maximum of 150 devices. If a network contains more
than 150 bus users, the search will be stopped after 150 devices. On the List informa-
tion menu, a List error is shown as List complete
• In the case of plant with several bus operator units, only one of them can make a
search run at a time
• A device search across all lines (Line =
own area
• Settings Area and Line must not be changed during the device search run.
• If a power failure occurs during a search run, or if the bus operator unit is removed
during a search run, the device list will be declared List invalid
• Commands are ignored as long as a device search run is in progress
• When creating the device list, the local names of the devices will be adopted by the
list. If, subsequently, the name is changed locally on the controller, the device list will
not automatically be updated
6.3.2

Submenu "Sort list"

• Sorting the device list in ascending device address order
• Sorting the device list in ascending device name order
• Sorting manually with the aim to have frequently operated devices at the beginning
of the list
Bus operator unit RMZ792
6 "Commissioning" menu
Description
Device list has been successfully
sorted
Device list has been successfully
deleted
Device search not possible with the
current settings of area and line
Range
0...15
* / 0...15
--- / Searched for
0...150
*
) is only possible in the bus operator unit's
Factory setting
0
2
---
0