Daikin AT12BV1LS Pocket Manual page 126

Service diagnosis split & multi
Table of Contents

Advertisement

Si10-417
Trouble
shooting
Check No.4
Refer to
P.151
Check No.6
Refer to
P.157
Service Diagnosis
Be sure to turn off power switch before connect or
Caution
disconnect connector, or parts damage may be occurred.
Any thermistor
disconnected?
NO
Stop valve closed?
NO
Check for gas leakage.
Oil
oozing at relay pipe
connections?
NO
Oil oozing at
internal piping?
NO
Check No.
Electronic expansion valve
functioning?
YES
Check the CT.
Functioning
Change for a specified amount
of fresh refrigerant.
Gas shortage
error again?
NO
YES
* Discharge pipe
thermistor
* Indoor / outdoor
unit heat
exchanger
thermistor
* Room temperature
thermistor
* Outdoor air
thermistor
YES
YES
YES
4
NO
Malfunctioning
YES
Troubleshooting
Reconnect in position.
Open the stop valve.
Repair the pipe flare
or replace the square
union.
A
Replace the electronic
expansion valve.
CT in trouble (refer to
H8).
B
Procedure complete