Technical Data (Modified 2002-10) - ABB SRIO 500M User Manual And Technical Description

Data communication and reporting unit
Table of Contents

Advertisement

Technical data
(modified 2002-10)
Serial interfaces
Serial interface 1:
Interface to host computer or
programming terminal
Serial interface 2:
Interface to SPA-bus
Serial inteface 4:
Interface to programming terminal or event printer
Event polling
Maximum number of units in the event poll list
Capacity of event buffer
Accuracy of time markings
Time resolution between events from
one serial interface
Time resolution between events from
two different serial interfaces
Data acquisition
Capacity of data base
System response time:
- EV-data from high priority slaves
- EV-data from normal priority slaves
- AI- or DI-data from slaves
Weigth
Power sources
Supply No. 1
Supply No. 2
Power consumptiont
Test voltages
- power supply inputs versus chassis
- relay outputs versus chassis
- opto-isolated inputs versus chassis
Dielectric test voltage as per
IEC 60255-5 and SS 436 15 03
Impulse test voltage as per
IEC 60255-5 and SS 436 15 03
High freguency test voltage as per
IEC 60255-5 and SS 436 15 03
Rated contact current/max. breaking
voltage of the relay outputs
Environmental conditions
Service temperature range
Storage temperature range
Maximum relative humidity (without condensation)
RS 232 C, max. 9600 b/s
(also current loop if used
as programming terminal)
RS 485, max. 9600 b/s
RS 232 C or current loop,
max. 9600 b/s.
100
500 events
1 ms
10 ms
50 ms
500 data items
amount of high priority slaves x 70 ms
amount of slaves x 200 ms
amount of cyclically polled data
items x 200 ms
about 8 kg
80...265 V dc or 17...70 V dc
80...265 V ac/dc
30 W
2 kV, 50 Hz, 1 min
5 kV, 1.2/50 µs, 0.5J
2.5 kV, 1 MHz
3 A/250 V, 50 Hz
0...+55 °C
-40...+70 °C
95 %