All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
GENERAL DESCRIPTION AIRCOOLAIR 200D & 230D 20S 140D Split ASC/ASH + CIC/CIH Condensing unit ASC/ASH OUTDOOR UNIT ASC / ASH 020S 025S 030S 035S 040S 045D 055D 070D 085D 100D 120D 140D 200D 230D A BOX B BOX C BOX D BOX INDOOR UNIT CIC / CIH...
Page 5
GENERAL DESCRIPTION INTRODUCTION AIRCOOLAIR range is developed from ECOLEAN liquid chiller range and exists in two versions: • AIRCOOLAIR SPLIT UNIT it can be used for medium to large commercial cooling and heating applications when the premises are not directly accessible from the roof. AIRCOOLAIR split unit exist in cooling only and heat pump versions.
A,B,C & D warm, in other words when the coil is not frozen. - Dynamic defrost is Lennox’ answers to unnecessary defrost cycles. Dynamic defrost detects icing of the coil by monitoring the difference between refrigerant and outside temperature and starts the defrost cycle only when required.
Page 7
GENERAL DESCRIPTION CONTROL The new generation of microprocessor based control, CLIMATIC It will also improve reliability with features such as compressor 60 equip the AIRCOOLAIR range. operating limits monitoring, (High and Low refrigerant pressure It inherits more than 20 years of technology and fi eld operating and temperature now measured and displayed on DS60 and experience from its predecessors Climatic control platforms.
Page 8
Quality manufacturing procedures together with a culture of continuous improvement at all LENNOX factories, ensures the products are built to the highest standards. AIRCOOLAIR complies to EN60204 norms, PED 97-23 directive, is CE compliant and is built in an ISO9001v2000 certifi...
OPTIONS FRESH AIR OPTIONS Economizer Return Module 020S - 045D 055D - 140D Free cooling is provided through the use of fresh air when it’s appropriate rather than cooling the return air. Using an economizer The RETURN FAN module is necessary when the return duct is the easiest and most effi...
Page 10
Stepped or modulating Electrical heaters Modulating Hot water coil : Additional or instead of heat pumps, Lennox offers many auxiliary This modulating heater is equipped with a 3 way valve offering heaters on every air-to-air units. This helps to adapt to local accurate comfort and electronic adjustable antifreeze protection.
Page 11
Because health and safety issue cannot be compromised, each schedule mode. Lennox equips its air treatment units (indoor unit) with a fi re-proof insulation M0 that is mechanically fi tted to the unit. Anti-vibration mounts rubber type (supplied loose)
Page 12
OPTIONS CONTROL AND COMMUNICATIONS OPTIONS DC60 remote comfort display (supplied loose) BE60 Extension control board This is a remote controller for non-technical customer. It has This board has been developed for any customer who wants to been designed to aesthetically fi t inside a room and be very easy take over the control of the unit using digital or analogue input to use.
Page 13
OPTIONS Models Legend : Split unit Condensing unit STD = As standard NSR = Non standard request N/A = Non available Cooling only Heat pump Cooling only Heat pump INDOOR SECTION : CIC AND CIH Economizer Exhaust module Return module Size 55 - 140 Fresh air over - Return bottom Size 20 - 45...
Page 14
OPTIONS Models Legend : Split unit Condensing unit STD = As standard NSR = Non standard request Cooling only Heat pump Cooling only Heat pump N/A = Non available OUTDOOR SECTION : ASC AND ASH Refrigeration option Winter cooling operation down to 0°C outdoor temperature Winter cooling operation down to -15°C outdoor temperature...
VENTILATION DATA TREATMENT VENTILATION DATA LARGE DUCTED SPLIT 100 Pa 150 Pa 200 Pa 250 Pa Airfl ow 3150 1x0,55 1x0,55 1x1,1 1x1,1 3425 1x0,55 1x0,55 1x1,1 1x1,1 3700 1x0,55 1x0,55 1x1,1 1x1,1 4100 1x0,55 1x1,1 1x1,1 1003 No kit 300 Pa 350 Pa 400 Pa...
Page 19
VENTILATION DATA TREATMENT VENTILATION DATA LARGE DUCTED SPLIT 100 Pa 150 Pa 200 Pa 250 Pa 300 Pa Airfl ow 6200 1x1,5 1x1,5 1x2,2 1x2,2 1x2,2 6650 1x1,5 1x1,5 1x2,2 1x2,2 1x2,2 7100 1x1,5 1x2,2 1x2,2 1x2,2 1x2,2 8050 1x1,5 1x2,2 1x2,2 1x2,2...
VENTILATION DATA TREATMENT VENTILATION DATA LARGE DUCTED SPLIT 100 Pa 150 Pa 200 Pa 250 Pa 300 Pa 350 Pa Airfl ow 9950 STD 1x2,2 666 STD 1x2,2 748 STD 1x2,2 828 1x3 1033 10825 STD 1x2,2 688 STD 1x2,2 770 1x3 1041 11700 STD 1x2,2 704...
Page 21
VENTILATION DATA TREATMENT VENTILATION DATA LARGE DUCTED SPLIT 100 Pa 150 Pa 200 Pa 250 Pa 300 Pa 350 Pa Airfl ow 17350 HP1 1x5,5 763 HP1 1x5,5 815 18875 HP1 1x5,5 777 HP1 1x5,5 827 20400 HP1 1x5,5 744 HP1 1x5,5 792 22450 HP1 1x5,5 721...
Page 22
VENTILATION DATA RETURN VENTILATION DATA Airfl ow (m Airfl ow (m 055D 070D 9950 10825 11700 12850 12450 13550 14650 15090 Airfl ow Airfl ow ASP PI ASP PI ASP PI ASP PI ASP PI ASP PI ASP PI ASP PI ( rpm) ↓...
Page 36
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES ASC 020S Air inlet temperature at condenser (wet bulb) 25 °C 30 °C 35 °C 40 °C 45 °C Evaporating temperature °C 17,3 5,27 16,8 5,55 15,9 6,01 14,7 6,67 13,5 7,42 20,3 5,49 19,8 5,71 18,6...
Page 37
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES ASC 030S Air inlet temperature at condenser (wet bulb) 25 °C 30 °C 35 °C 40 °C 45 °C Evaporating temperature °C 25,4 7,94 24,7 8,25 23,0 9,11 21,1 10,1 19,1 11,2 29,7 8,20 28,8 8,60 26,8...
Page 38
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES ASC 040S Air inlet temperature at condenser (wet bulb) 25 °C 30 °C 35 °C 40 °C 45 °C Evaporating temperature °C 37,5 11,6 36,6 12,0 34,3 13,2 31,8 14,5 29,1 16,0 44,3 11,8 42,4 12,6 39,7...
Page 39
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES ASC 055D Air inlet temperature at condenser (wet bulb) 25 °C 30 °C 35 °C 40 °C 45 °C Evaporating temperature °C 50,8 15,9 49,4 16,5 45,9 18,2 42,2 20,2 38,2 22,4 59,5 16,4 57,5 17,2 53,5...
Page 40
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES ASC 085D Air inlet temperature at condenser (wet bulb) 25 °C 30 °C 35 °C 40 °C 45 °C Evaporating temperature °C 74,9 23,3 73,3 24,1 68,6 26,5 63,6 29,1 58,3 31,9 88,6 23,6 84,9 25,3 79,4...
Page 41
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES ASC 120D Air inlet temperature at condenser (wet bulb) 25 °C 30 °C 35 °C 40 °C 45 °C Evaporating temperature °C 30,8 99,0 32,2 93,4 35,0 86,6 38,5 79,3 42,4 31,8 33,2 36,4 40,1 92,5 44,1...
Page 42
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES ASC 200D Air inlet temperature at condenser (wet bulb) 25 °C 30 °C 35 °C 40 °C 45 °C Evaporating temperature °C 52,7 54,6 59,4 65,3 72,0 54,7 56,7 62,1 68,3 75,3 55,1 57,9 63,4 69,6 76,6...
Page 43
PERFORMANCES - CONDENSING UNIT COOLING CAPACITIES HIGH AMBIENT APPLICATION (Non standard request) ASC 085D Air inlet temperature at condenser (wet bulb) 46 °C 47 °C 48 °C 49 °C 50 °C Evaporating temperature °C 57,0 32,6 55,9 33,2 54,7 33,8 53,5 34,5 52,4...
PERFORMANCES - CONDENSING UNIT EXTRA POWER CONSUMPTION Cooling and heating modes MODELS 100D 120D 140D 200D 230D Low speed 14.2 10.4 High speed OPERATING LIMITS Maximum temperatures Minimum temperatures Cooling only units Indoor temperature 32°C DB / 23°C WB 21°C DB / 15°C WB 45°C Cooling operation (020S-025S-030S-045D-055D)
AUXILIARY HEATERS SELECTION HOT WATER COIL Capacity according to the gap Air pressure drop between water inlet and air Water coil INDOOR Water inlet temperature pressure Weight Water UNIT fl ow Nr of drop outlet rows diameter CIC/CIH Nominal Minimum airfl...
ACOUSTIC DATA NOISE LEVEL OF INDOOR UNITS - IN DUCT STANDARD / HP1 / HP2 / HP3 UNITS Spectrum per octave band (dB(A)) Sound pressure Sound power 10 meters from the CIC/CIH unit 63 Hz 125 Hz 1000 2000 4000 8000 LW dB(A) Lp dB(A)
Page 48
ACOUSTIC DATA NOISE LEVEL OF INDOOR UNITS - IN DUCT STANDARD / HP1 / HP2 / HP3 UNITS + RETURN FAN Spectrum per octave band (dB(A)) Sound pressure Sound power 10 meters from the CIC/CIH unit 63 Hz 125 Hz 1000 2000 4000...
Page 49
ACOUSTIC DATA NOISE LEVEL OF OUTDOOR UNITS STANDARD UNITS Spectrum per octave band (dB(A)) Sound pressure Sound power 10 meters from the ASC/ASH unit 125 Hz 1000 2000 4000 8000 LW dB(A) Lp dB(A) 020S 67,6 70,6 71,2 71,1 69,2 67,0 59,1 75,9...
Page 50
ACOUSTIC DATA NOISE LEVEL OF OUTDOOR UNITS UNITS WITH HIGH PRESSURE OPTION (FP1) Spectrum per octave band (dB(A)) Sound pressure Sound power 10 meters from the ADC/ADH unit 125 Hz 1000 2000 4000 8000 LW dB(A) Lp dB(A) Low speed 84,2 80,6 80,5...
ELECTRICAL CONNECTIONS - Before making any electrical connections, be sure that all circuit breakers are open. - In order to carry out the electrical connections, follow the electrical diagram suppied with the unit. INDOOR SECTION DADS HR/T LDRP DIFS Electrical box HR/T Note: The length of all cables for connection with indoor OUTDOOR SECTION...
ELECTRICAL CONNECTIONS POWER SUPPLY Power supply Power supply with Power supply Free-cooling Exhaust fan Return fan electrical heater 1’ 020S 4 x 4 mm² 4 x 10 mm² 4 x 1,5 mm² 7 x 1,5 mm² 3 x 1,5 mm² 025S 4 x 6 mm²...
Page 55
ELECTRICAL CONNECTIONS COMFORT AND SERVICE TERMINAL CONNECTION DRY CONTACT BOARD CONTROL The AIRCOOLAIR condensing unit can be remotely controlled via dry contacts on the BM60 and BE60. The expansion board BE60 is an additional board fi xed on DIN rail. This board is supplied in stand on AIRCOOLAIR condensing unit.
Page 57
DIMENSIONAL DATA OUTDOOR UNITS - ASC/ASH 020S 025S/030S/035S/040S 1 1 9 6 6 0 045D/055D/070D/085D 100D/120D/140D 200D - 230D Main switch (option) Power supply cable entry Electrical box Access to gas and liquid lines Application Guide • AIRCOOLAIR-AGU-1603-E • 55 •...
Page 58
DIMENSIONAL DATA ECONOMIZER + EXHAUST FANS 020S/025S/030S/035S/040S/045D A BOX & B BOX Indoor unit Outdoor air Exhaust fan Exhaust fan (Front view) (Rear view) . 5 5 8 7 .5 4 0 2 3 9 0 Mixing section 5 0 0 5 0 0 5 0 0 Return air...
Page 59
DIMENSIONAL DATA UNITS WITH HIGH PRESSURE FANS Electrical box o 800 Main switch (option) This option is available only for outdoor units, sizes 100D, 120D and 140D. Available static pressure up to 250 Pa. Access to gas and liquid lines 2 2 5 1 4 2 Power supply...
REFRIGERANT CONNECTIONS To locate the outdoor and the indoor units, refer to the following information : Outdoor unit Indoor Outdoor unit unit As standard, distance between indoor and outdoor units is 40 meters. This distance reaches 65 meters with long distance option. V Maximum length = 16 meters L : Maximum total length (vertical + horizontal = 65 meters) Indoor unit...
Page 62
LENNOX DISTRIBUTION PORTUGAL +33 4 72 23 20 20 +351 229 066 050 Due to Lennox’s ongoing commitment to quality, the specifi cations, ratings and dimensions are subject to change without notice and without incurring liability. Improper installation,...