Chapter 5. Diagnostics

5.1 Status Data

The GGC001 produces a total of 96 bits (12 bytes) to supply status information to the controlling PROFINET
Controller. When ultimately controlled by an RX3i PLC, these reference bits consume a total of 96 reference
address bits in %I memory. The 96 bits consist of
32 bits related to the operation of the GCG001 itself - referred to in PME as Gateway Status Data,
and
32 bits related to the online status of the Genius bus which it controls – referred to as Genius
Status Data in PME, and
32 bits related to any faults that are associated with a device – referred to as Fault Status Data in
PME.
Each bank of 32 bits must be assigned a different set of Input reference addresses in RX3i memory.
For each bank of 32 status bits, a default beginning reference (the next available %I) for the status bits is
automatically assigned by PME. These assignments may be changed by clicking on the GCG001 and keying in
different %I references.

Gateway Status Data

For the Genius Gateway GCG001, the thirty-two bits in the Gateway Status Data are organized as follows,
beginning at the first %I status reference assigned to this bank of 32:
Bit#
Name
0
Module OK
1
Fault Present
2
Port1 Link Up
3
Port2 Link Up
4-9
Reserved
10
MRP Enabled
11
MRP Role
12-31
Reserved
42

Figure 24: Gateway Status Data

Bit Condition
Meaning of Status Bit
OFF
The GCG001 module is powering up or has failed.
ON
Indicates the GCG001 module is functioning properly.
OFF
No GCG001 diagnosis data available; FAULT LED is Off.
ON
GCG001 diagnosis data is available; FAULT LED is On.
Port is not connected to a properly configured device, or
OFF
port is experiencing communications errors.
ON
Port is connected to another device and is communicating.
Port is not connected to a properly configured device, or
OFF
port is experiencing communications errors.
ON
Port is connected to another device and is communicating.
OFF
Always off
ON
N/A
OFF
MRP is not enabled
ON
MRP is enabled
Indicates that the GCG001 is an MRP Client (if MRP is
OFF
enabled), or that MRP is not enabled.
Indicates role is that of an MRP Manager – this is not a
ON
possible role for the GCG001.
OFF
Always off
ON
N/A
PACSystems RX3i Genius Communications Gateway
GFK-2892F