Excess Conditions; Excess Temperature/Power Failure; Low Water/Excess Water Pressure - Viessmann Vitoflex RF 150 Installation And Service Instructions Manual

Wood-fired boiler, output range: 154/205/273/341/478-512/751/1024/1365/1843 mbh, 45/60/80/100/140-150/220/300/400/540 kw
Table of Contents

Advertisement

Vitoflex 300-RF Installation & Operating

Excess Conditions

IMPORTANT

Excess temperature/power failure

CAUTION
DANGER OF THIS EQUIPMENT SUDDENLY GOING UP
IN FLAMES:
DO NOT open the doors or lids on the boiler plant!
- Switch on additional heat loads.
- The flue gas exhaust blower shuts down.
- The temperature-limiting safety switch triggers.
- The thermal safety flush valve opens at approximately
203°F (95°C). The excess heat is being dissipated
into the drain.
IMPORTANT
If the fixed high limit has triggered, it has to be manually
unlocked.
The fixed high limit is situated at the top of the boiler.
To reset, unscrew the black cap and press the button.
Note: Resetting is only possible when the temperature
has fallen to approx. 158°F (70°C).
Possible causes for excess temperature:
- Incorrect setting on the control module.
- Defective component of the system (pump or valve).
- Sudden drop in output to zero. The in-feed auger still
has to be emptied. The heat yet produced by this can
result in surplus temperature.
Activate "DISSIPATE SURPLUS HEAT" function!

Low water/excess water pressure

Possible causes:
- Low water: Leakage in the heating system.
- Excess water pressure: The expansion tank is not
functioning.
In either case, the boiler should be examined by a qualified
heating contractor.
Note: Unlock this malfunction with either the reset button
for the water level control system or for the
overpressure monitor, and by pressing the OK
button on the control panel.
Operation
51

Advertisement

Table of Contents
loading

Table of Contents