Model TZC-8B
Telephone Zone Card
INTRODUCTION
OPERATION
Controls and Indicators
P/N 315-034110-6
A24205-A334-B821
The Model TZC-8B Telephone Zone Card from Siemens
Industry, Inc., provides a way for emergency response
personnel located throughout a building to speak with one
another during emergency situations. The card is located in
any FireFinder-XLS enclosure and is connected to jacks or Fire
Fighter's Telephone Stations located throughout the building.
Portable phones (Models PFT and PFT-P) that plug into
these jacks or Fire Fighter's Telephone Stations (Model FTS)
can communicate to the Model FMT Fireman's Master
Telephone located at the main enclosure or to telephones
connected to the system.
Each TZC-8B module provides eight telephone zones. The
TZC-8B module connects to the emergency telephones or
telephone jacks located throughout a building through the
eight telephone zones. In addition, it is also connected to
the phone riser and to the CAN bus which the system uses
to control the TZC-8B.
In normal operation, the TZC-8B monitors the inputs of the
eight zones to detect if one of the connected phones is off
hook or "jacked in" . When this is detected, the TZC-8B
transmits a message to the system via the CAN bus. The
system indicates the call on the front panel. Depending on
operator action, a message is sent back to the TZC-8B to
connect the zone through to the phone riser.
All the TZC-8B zone circuits are supervised for Class B
(Style Y) use only.
The front panel of the TZC-8B contains one reset switch, 20
LEDs, and two CAN address switches as shown in Figure 1.
A reset switch is located on the top of the front panel.
Pushing the reset switch re-initializes the TZC-8B operation.
Figure 1
TZC-8B Telephone
Zone Card
Siemens Industry, Inc.
Building Technologies Division
TZC-8B
RESET
POWER
CARD FAIL
CAN FAIL
GND FAULT
ZONE 1 ACTIVE
TRBL
ZONE 2 ACTIVE
TRBL
ZONE 3 ACTIVE
TRBL
ZONE 4 ACTIVE
TRBL
ZONE 5 ACTIVE
TRBL
ZONE 6 ACTIVE
TRBL
ZONE 7 ACTIVE
TRBL
ZONE 8 ACTIVE
TRBL
TENS
ONES
CAN

Advertisement

loading

Summary of Contents for Siemens TZC-8B

  • Page 1: Installation Instructions

    In normal operation, the TZC-8B monitors the inputs of the eight zones to detect if one of the connected phones is off TENS hook or “jacked in” . When this is detected, the TZC-8B ONES transmits a message to the system via the CAN bus. The system indicates the call on the front panel.
  • Page 2 (Refer to Figure 1 for the location of the switches.) The address selected at the front panel of the TZC-8B must be the same as the address selected in the Zeus program- ming tool. To set the address, turn the pointers on both of the two dials to the numbers for the selected address.
  • Page 3 Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.) All field wiring to the TZC-8B is connected to the terminal blocks of the CC-5 card cage slot in which it is installed (refer to Figure 2).
  • Page 4 INSTALLATION The TZC-8B plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN connectors and can occupy any slot in the card cage. Insert the TZC-8B card into the card guides rightside up (lettering on the front panel is legible).