Summary of Contents for Pentair Pool Products Pentek SPP-235P
Page 1
INSTALLATION INSTRUCTIONS Submersible Pump Protector MODEL SPP-235P 293 Wright Street, Delavan, WI 53115 (866) 9-PENTEK...
Page 2
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION. The SPP-235P Single-phase Submersible Pump Protector is a pump monitor designed to protect single-phase pumps from dry-well, dead-head, rapid-cycle, jammed impeller, and over/under voltage conditions.
Page 3
Size Current 5-7 ½ HP 27.5 – 42.1 50:5 10 HP 75:5 15 HP 100:5 TABLE 1: Current Transformer Selection FIGURE NO.1: Typical Wiring Diagram...
OPERATION The Submersible Pump Protector monitors pump load in amps and kilowatts. When the current (amps) exceeds approximately 125% of calibrated current, or power (kW) drops below the adjustable underload trip point, the Submersible Pump Protector—after the trip delay—will turn off the pump.
Page 6
RUN HOURS / FAULT HISTORY The Submersible Pump Protector records pump run hours and the last 20 faults. These values can be displayed by an Informer (see USING AN INFORMER). Run hours and fault history can be cleared on the Submersible Pump Protector. Read the following instructions fully before performing he procedure.
Page 7
To Enable Line-Side/Upstream Rapid-Cycle Protection: (to disable, follow the same procedure) 1. Remove power to the Submersible Pump Protector. 2. Set the RESTART DELAY/ CALIBRATION knob to RESET and the SENSITIVITY knob to the middle (12:00) position. 3. Apply power to the Submersible Pump Protector —the CAL. LIGHT will turn on. 4.
TROUBLESHOOTING RUN LIGHT CAL. LIGHT PROBLEM or FUNCTION CORRECTIVE ACTION RUN: On Steady Pump is running—or ready to run— None no problems in operation CAL: The Submersible Pump Protector On Steady On Steady None is in the calibration process. CAL COMPLETE: The Submersible Pump Protector Pump will restart as soon as is calibrated;...
SPECIFICATIONS Functional Specifications Adjustments/Settings Overcurrent 125% of calibration point Underload (dry-well) Adjustable (70-90% of calibrated run power) Overvoltage 265VAC Undervoltage 190VAC Number of restarts allowed in 60 second period (rapid-cycling) Trip Delay Times Overcurrent 5 seconds Dry-well 4 seconds Restart Delay Times Over/undervoltage 2 seconds All other faults...
LIMITED WARRANTY Goods manufactured/sold by Pentek are subject to the following Limited Warranty, which is in lieu of, and excludes all other warranties, guarantees and conditions expressed or implied, unless stated otherwise. Goods are warranted to be free from defects in workmanship or material for a period of 5 years from the date of manufacture provided such goods have not been subjected to misapplication, misuse, negligence or repairs by unauthorized persons.