Securing The Outdoor Unit; Refrigerant Piping Connections - Lennox MHA Series Installation Instructions Manual

Hide thumbs Also See for MHA Series:
Table of Contents

Advertisement

The conduit must be designed so it cannot collect and
retain water.

Securing the Outdoor Unit

Slab or Roof Mounting
Install the unit a minimum of 4 inches (102 mm) above
the roof or ground surface to avoid debris build­up around
the unit. Place the unit above a load bearing wall or area
of the roof that can adequately support the unit. Consult
local codes for rooftop applications.
CAUTION
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil. This will cause
the rubber to swell when it comes into contact with oil.
The rubber will then bubble and could cause leaks.
Protect the roof surface to avoid exposure to refrigerant
and oil during service and installation. Failure to follow
this notice could result in damage to roof surface.
Securing Outdoor Unit to Slab, Frame, or Rails
If the outdoor unit is installed on a field-provided slab or
frame, use lag bolts or equivalent to secure the outdoor
unit to the slab or frame.
Four Field-provided Anchor Bolts
Figure 26. Securing Outdoor Unit to Slab
Figure 27. Securing Outdoor Unit to Rails
Securing Outdoor Unit to Hanging Brackets
If the outdoor unit is installed on field-provided wall
mounting brackets, use lag bolts or equivalent to secure
the outdoor unit to the bracket. Minimum rear clearance
can be reduced to 6 inches (152 mm) when mounted
on brackets and with no obstructions on the other three
sides. Allow for moisture disposal when placing units
above one another.
Four Field-Provided
Anchor Bolts
Air Outlet
Figure 28. Securing Outdoor Unit to Brackets

Refrigerant Piping Connections

Field piping consists of two copper lines connecting the
outdoor unit to the indoor unit. "Table 5. Refrigerant Piping
and Indoor Unit Connection Sizes" on page 12 lists
the connection sizes. The connections are made using
the provided brass flare nuts at the end of the refrigerant
piping connections.
1. Choose the correct pipe sizes for your application
using "Table 5. Refrigerant Piping and Indoor Unit
Connection Sizes" on page 12.
2. Confirm that you are using the correct diameter piping.
3. Determine the necessary piping length required for
the application.
4. Cut the selected pipes with a pipe cutter. Make the
cuts flat and smooth as illustrated in "Figure 29.
Cutting Piping".
Figure 29. Cutting Piping
5. Insulate the copper piping.
6. Insert a flare nut onto each pipe before flaring.
7. Use "Table 4. Flaring Pipe" to properly flare the pipe.
11
6 in
152 mm
Air Inlet
Lean
Crude
Burr

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents