Measured value
acquisition and
measured signal
Note
42 / 84
Siemens
Building Technologies
8.2.2
Active sensors DC 0 ... 10 V
The active sensors use a signal amplifier which emits a standard DC 0...10 V
signal. This voltage range is proportional to the application range of the sensor.
Active sensors are available for:
– Relative humidity
– Pressure in liquid and gaseous media
– Differential pressure in liquid and gaseous media
– Air quality
– Air velocity
U
10 V
0 V
0 %
When the process value is outside -1.5...11.5 V, a fault message will be sent.
For a workaround (Zener diode), see CM110563.
Desigo TRA Engineering, mounting and installation
Electrical features of inputs & outputs
Key
U
Sensor signal (voltage)
x
Measured value
(0...100% = application range)
100 %
x
CM111043en_09
2016-02-22