Horizontal flue terminal positions
300
3
300
11
300
1500
1200
BOUNDARY LINE
1
100
25
200
BOUNDARIES
1/2
1/2
Fig. 30 Horizontal flue terminal positions
Key to figure 30:
[1]
200mm below eaves and 75mm below gutters, pipe and drains.
[2]
The dimension below eaves, gutters, pipes and drains can be
reduced to 25mm, as long as the flue terminal is extended by
100mm past any overhang. The telescopic flue joint must be
sealed with suitable silicone sealant if it is external to the building.
[3]
300mm adjacent to a boundary line, unless it will cause a
nuisance. BS 5440: Part 1 recommends that care is taken when
siting terminal in relation to surfaces or boundary lines.
[4]
1,200mm separation measured between terminals facing each
other.
[5]
600m distance to a surface or boundary line facing a terminal,
unless it will cause a nuisance. BS 5440: Part 1 recommends that
care is taken when siting terminal in relation to surfaces or
boundary lines.
Greenstar 8000 Style – 6720883855 (2019/01)
10
BOUNDARY LINE
300
OPENING
3
OPPOSITE
14
2000
600
5
8
1200
300
11
300
5
600
300
1000
4
13
2
200
75
25
25
9
25
100
25
25 100
25 100
DORMA
SKYLIGHT
TOP
600
600
TOP
1
200
300
7
300
300
600
11
10
300
300
1
BELOW GROUND OPEN LIGHT WELL
<1000
300
300
75
300
2
150
25
[6]
The terminal must be at least 1500mm from the opening or vent
when sited below the window or 600mm when sited to either side
or above.
[7]
600mm diagonally to an opening door, air vent or opening
window.
[8]
1,200mm separation between a vertical flue measured
horizontally and a horizontal flue terminal.
Not required if the horizontal flue is 1,200mm above.
[9]
For the purpose of determining suitable flue terminal positions for
gas appliances, the boundary can be considered to extend to the
centre line of any adjacent routes or waterways e.g. paths,
streets, rights of way, canals, rivers or railways.
[10] 300mm to an internal or external corner. 300mm above a
surface, such as the ground/ floor level or roof surface.
* If the terminal section is less than 150mm and has two screws
securing it to the elbow, the terminal section will not require a
supporting bracket.
6
600
600
600
1500
200
1
10
300
10
25
300
12
600
15
300
Pre-Installation
6
5
600
16
100
25
10
300
0010021442-001
21