Multi-Split Communication Wiring Check
The FlexFit Multi and Arctic multi systems are capable of performing a self-test to check
communication wiring between the outdoor to the indoor units. This is a crucial step when performing
start-up on a system as well as performing checks during a service call. It allows you to confirm that
the wiring matches with the associated refrigerant lines for a given circuit.
Models affected:
Arctic Multi
2U20EH2VHA
3U24EH2VHA
FlexFit Multi 3U24MS2VHB
4U36MS2VHB
Instructions:
1. Disconnect power to the outdoor unit.
2. Set Dip Switches SW1-1, SW1-2, SW1-3 &
SW1-4 to the ON position. These dip
switches are located on the Service Monitor
Board. (pictured right).
3. Turn ON power to the outdoor unit.
Service Bulletin
1
JUNE 2019
DFS05-19
SW1
DFS05-19

Advertisement

loading

Summary of Contents for Haier Arctic Multi Series

  • Page 1 JUNE 2019 DFS05-19 Service Bulletin Multi-Split Communication Wiring Check The FlexFit Multi and Arctic multi systems are capable of performing a self-test to check communication wiring between the outdoor to the indoor units. This is a crucial step when performing start-up on a system as well as performing checks during a service call.
  • Page 2 JUNE 2019 DFS05-19 Service Bulletin Testing Process: All indoor fans will come on at HIGH fan speed. EEV for Circuit A will open. All other EEV’s will close. After a 3 minute delay, the Compressor will start and ramp up to 55HZ. The digital display will alternately display “CH”...
  • Page 3 JUNE 2019 DFS05-19 Service Bulletin Testing Process (continued): Once all indoor units have been checked, the digital display will show either “EC” or “0” • “EC” indicates there is an error in the wires to the indoor unit(s). • The LED(s) will be flashing, indicating which circuit(s) has the fault. •...